Industrial Automation

Meccatroinca

Mechatronics

Industrial Safety

Panel Components

Sensors and Systems of Vision

Pneumatics

Network Comunications

Automation Cables

Access services

Enter your reserved area

Access services

Enter your reserved area

PHOENIX CONTACT 2744652
PHOENIX CONTACT 2744652
PHOENIX CONTACTNot available

PSM-CABLE-PROFIB/FC - Bus system cable

By the meter, Bus system cable, PROFIBUS (12 Mbps), shielded, PVC FR VI/PVC, violet, 2-wire (1x2xAWG22/1), color single wire: red, green, cable length: Free entry (1.0 ... 1000.0 m)
Product Code: 2744652 copia - copy
Partner cod.: 2744652 copia - copy
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Tecnichal data
Download
Tecnichal data
Product propertiesProduct type: Data cable by the meter
Sensor type: PROFIBUS
Number of positions: 2
Shielded: yes
Electrical propertiesNominal voltage UN: 48 VÂAC
60 VÂDC
Transmission medium: Copper
InterfacesSignal type/category: PROFIBUS, 12 Mbps
Cable/lineCable length: Free entry (1.0 ... 1000.0 m)
Cable weight: 80 kg/km
UL AWM Style: 21694 (60°C / 600ÂV)
Wiring standards/regulations: Conductor material DINÂENÂ13602 Cu-ETP-A...
Shielding material DINÂENÂ13602 Cu-ETP-A...-B
Number of positions: 2
Shielded: yes
Conductor structure: 1x2xAWG22/1
Signal speed: 0.81 c
Conductor structure signal line: 1x 0.65 mm
AWG signal line: 22
Conductor cross section: 2x 0.34 mm²
Wire diameter incl. insulation: 2.55 mm
External cable diameter: 8 mm ±0.4Âmm
Outer sheath, material: PVC FR VI
External sheath, color: violet
Conductor material: Bare Cu wire
Material wire insulation: PE
Single wire, color: red, green
Thickness, insulation: 0.95 mm
Thickness, outer sheath: 0.9 mm
Overall twist: 2 wires, twisted
Optical shield covering: 55 %
Insulation resistance: ≥ 16 GΩ*km
Loop resistance: ≤ 110.00 Ω/km
Cable capacity: approx. 28.5 nF/km (at 1 kHz)
≤ 1500 pF/km (asymmetrical: Conductor to ground)
Cable impedance: 150 Ω ±10Â% (3 ... 20 MHz)
185 Ω ±10Â% (31.25 ... 38.4 kHz)
270 Ω ±10Â% (9.6ÂkHz)
Test voltage: 3600 VÂDC (3 s)
Smallest bending radius, fixed installation: ≥ 150 mm
Tensile strength: ≤ 100 N
Shield attenuation: ≤ 42 dB/km (at 16 MHz)
≤ 22 dB (at 4 МHz)
≤ 4 dB (at 38.4 kHz)
≤ 2.5 dB (at 9.6 kHz)
Flame resistance: according to IEC 60332-3-24 (Cat. C )
according to CMGÂFT4
Resistance to oil: Limited resistance to mineral oils and greases
according to IEC 60811-2-1, 4Âh at 70°C
Other resistance: Cold bending resistance according to DINÂVDEÂ0473 PartÂ811-1-4 (after 16Âh at -40°C)
UV resistant CL3 SUN RES
Ambient temperature (operation): -40°C ... 60°C
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Data_sheet_03436.pdf

Manufacturer_declaration_01381.pdf

Manufacturer_declaration_02425.pdf