PHOENIX CONTACT 1033482
PHOENIX CONTACTNon disponibile

PACT RCP-D140-10M - Coil

Rogowski coil, The Rogowski coil measures the AC current of rails and power lines.
Cod. Articolo: 1033482 copia - copy
Cod. Fornitore: 1033482 copia - copy
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Download
Caratteristiche Tecniche
Product propertiesProduct type: Rogowski coil
Insulation characteristics
Pollution degree: 2
Electrical propertiesMeasuring coil
Conductor structure signal line: 2x 0.22 mm (Signal (tinned))
1x 0.22 mm (Shielding (tinned))
Insulation: double insulation
Rated insulation voltage: 1000 VÂAC (rms CAT III)
600 VÂAC (rms CAT IV)
Test voltage: 10.45 kV DC (60 s)
Basic accuracy: <± 0.2 %
General
Converter type: Rogowski coil
Input dataFrequency
Designation: Measuring coil
Frequency measuring range: 40 Hz ... 20000 Hz
Position error: <± 0.1 % (typical)
Linearity error: < 0.1 %
Current transformers
Converter type: Rogowski coil
Output dataSignal
Designation: Measuring coil
Output signal (at 50 Hz): 100 mV (no load, at 1,000 A)
Output voltage (in no-load operation): VOUT = M * dI/dt
Output voltage (sinusoidal, in no-load operation): 100 mV (VOUT = 2 * Ï€ * M * f * I (M = 0.318 μH; example: At 50 Hz; I = 1,000 A))
DimensionsMeasuring coil
Length: 450 mm
Diameter: 8.3 mm ±0.2Âmm
Measuring coil when installed
Diameter: 140 mm
Signal line
Length: 10 m
Material specificationsCoil material: Elastollan
Housing material: PC
Environmental and real-life conditionsAmbient conditions
Measuring coil degree of protection: IP67 (not assessed by UL)
Ambient temperature (operation): -30°C ... 80°C (Measuring coil)
Ambient temperature (storage/transport): -40°C ... 80°C (Measuring coil)
Altitude: < 2000 m
Permissible humidity (operation): 5 % ... 95 % (non-condensing)
ApprovalsUKCA
Certificate: UKCA-compliant
CMIM
Certificate: CMIM-compliant
UL, USA/Canada
Identification: UL 61010 Recognized
Note: Measuring coil
Standards and regulationsStandards/regulations: IEC 61010-1
IEC 61010-2-032