IOA PR-DAI/DAO/F/DS/2A/EX - Input/output module

Fuse module for VIP I/O marshalling base elements with replaceable 2A fuse in the field device supply path. Integrated test points and a disconnect knife allow uninterrupted signal measurement.
Cod. Articolo: 1048208 copia - copy
Cod. Fornitore: 1048208 copia - copy
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Download
Caratteristiche Tecniche
Product propertiesProduct type: Interface module
Product family: VIP I/O-Marshalling
Number of positions: 1
Insulation characteristics
Overvoltage category: II
Pollution degree: 2
Electrical propertiesMax. operating voltage Umax: 30 V
Max. permissible current: 1 A (Signal)
Max. total current of voltage supply: 2 A (1048208 fuse limited)
0.25 A (1188706 fuse limited)
Ex dataSafety data
Input voltage Ui: 30 V
Input current Ii: 1 A
Inductance Li: 0 mH
Capacitance Ci: 0 µF
Max. output voltage Uo: Ui
Max. output current Io: Ii
Max. output power Po: Pi
DimensionsItem dimensions
Width: 10.3 mm
Height: 64.2 mm
Depth: 72.9 mm
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -40°C ... 75°C
Ambient temperature (storage/transport): -40°C ... 75°C
Altitude: ≤ 2000 mm
Permissible humidity (operation): 0 % ... 95 % (non-condensing)
ApprovalsATEX
Identification: ïÃ‹œ II 3G Ex ec IIC T4 Gc
ïÃ‹œ II 3G Ex ic IIC T4 Gc
Certificate: CSANe 20ATEX3152X
IECEx
Identification: Ex ec IIC T4 Gc
Ex ic IIC T4 Gc
Certificate: IECEx SIR 21.0005X
UKEX
Identification: ïÃ‹œ II 3G Ex ec IIC T4 Gc
ïÃ‹œ II 3G Ex ic IIC T4 Gc
Certificate: PxCIF23UKEX1048208X
CSA, USA/Canada
Identification: Class I, Div. 2, Groups A, B, C, D
Class I, Zone 2, AEx ic IIC T4 Gc
ANIFW apparatus for connection to:
Class I, II, III, Div. 2 Groups A, B, C, D, F, G
Ex ic IIC T4 Gc
Ex ec IIC T4 Gc
Certificate: CSA 21CA80047687X
Standards and regulationsStandards/regulations: IEC 60664
DINÂENÂ50178
MountingMounting type: Plug-in mounting
Assembly instructions: Plugs into VIP/...BASE...
Mounting position: any
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00795.pdf

Approvals_00796.pdf

Approvals_00797.pdf

Manufacturer_declaration_04413.pdf

Package_slip_00150.pdf

Product_information_00031.pdf

Product_information_00033.pdf

Technical_drawing_06606.pdf