Automazione Industriale

Meccatroinca

Meccatronica

Sicurezza Industriale

Componenti Quadri

Sensori e Sistemi di Visione

Pneumatica

Network e Comunicazione

Cavi Speciali

Accedi ai servizi

Entra nella tua area riservata

Accedi ai servizi

Entra nella tua area riservata

PHOENIX CONTACT 1110043
PHOENIX CONTACT 1110043
PHOENIX CONTACTNon disponibile

UNO2-PS/1AC/24DC/960W - Power supply unit

Primary-switched power supply unit, UNO POWER, Screw connection, DIN rail mounting, input: 1-phase, output: 24 V DC / 40 A, adjustable from 24 V DC ... 28 V DC
Cod. Articolo: 1110043 copia - copy
Cod. Fornitore: 1110043 copia - copy
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Descrizione
Caratteristiche Tecniche
Input dataAC operation
Supply system configuration: Star network (TN, TT, IT (PE))
Nominal input voltage range: 100 V AC ... 240 V AC
Input voltage range: 100 V AC ... 240 V AC -15 % ... +10 %
110 V AC ... 240 V AC ±10 % (UL)
Derating: < 99 V AC (1 %/V)
Typical national grid voltage: 120 V AC
230 V AC
Voltage type of supply voltage: AC
Inrush current: typ. 15 A (at 25 °C)
Inrush current integral (I2t): < 0.5 A2s
Frequency range (fN): 50 Hz ... 60 Hz ±10 %
Mains buffering time: typ. 17 ms (120 V AC)
typ. 23 ms (230 V AC)
Current consumption: 10.5 A (100 V AC)
9 A (120 V AC)
4.7 A (230 V AC)
4.5 A (240 V AC)
9.5 A (110 V AC (UL))
4.5 A (240 V AC (UL))
Protective circuit: Transient surge protection; Varistor, gas-filled surge arrester
Switch-on time: typ. 1 s
Device mains fuse: 20 A internal (device protection), slow-blow
Recommended breaker for input protection: 10 A ... 16 A (Characteristic B, C, D, K or comparable)
Discharge current to PE: < 3.5 mA
Output dataEfficiency: typ. 93.6 % (120 V AC)
typ. 94.8 % (230 V AC)
Nominal output voltage: 24 V DC
Setting range of the output voltage (USet): 24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN): 40 A
Short-circuit-proof: yes
No-load proof: yes
Derating: 55 °C ... 70 °C
Crest factor: typ. 1.6 (120 V AC)
typ. 1.6 (230 V AC)
Output power (PN): 960 W
Connection in parallel: yes, for redundancy
Connection in series: yes, for increased output voltage
Feedback voltage resistance: ≤ 35 V DC
Protection against overvoltage at the output (OVP): ≤ 35 V DC
Residual ripple: typ. 150 mVPP (with nominal values)
Control deviation: < 1 % (change in load, static 10 % ... 90 %)
< 3 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Rise time: < 1 s (UOut = 10 % ... 90 %)
Minimum no-load power dissipation: < 5 W (120 V AC)
Maximum no-load power dissipation: < 4 W (230 V AC)
Minimum nominal load power dissipation: < 67 W (120 V AC)
Power loss nominal load max.: < 53 W (230 V AC)
Signal relay 13/14
Connection level: 3.x
Connection labeling: 3.1 (13), 3.2 (14)
Switch contact (floating): OptoMOS
Switching voltage: max. 30 V AC/DC
max. 60 V DC
Current carrying capacity: max. 50 mA
State condition: DC OK (UOut > 0,9 x UN) (Contact closed)
UOUT < 0,9 x UN (Contact open)
Connection dataInput
Position: 1.x
Identification: 1.1 (), 1.2 (L), 1.3 (N)
Conductor connection
Connection method: Screw connection
rigid: 0.2 mm² ... 6 mm²
flexible: 0.2 mm² ... 4 mm²
flexible with ferrule without plastic sleeve: 0.25 mm² ... 4 mm²
flexible with ferrule with plastic sleeve: 0.25 mm² ... 4 mm²
rigid (AWG): 24 ... 10 (Cu)
Stripping length: 8 mm
Tightening torque: 0.5 Nm ... 0.6 Nm
4 lbf-in. ... 5 lbf-in.
Drive form screw head: Slotted L
Output
Position: 2.x
Identification: 2.1, 2.2 (+), 2.3, 2.4 (-)
Conductor connectionâۉ€¹
Connection method: Screw connection
rigid: 0.5 mm² ... 16 mm²
flexible: 0.5 mm² ... 16 mm²
flexible with ferrule without plastic sleeve: 0.5 mm² ... 16 mm²
flexible with ferrule with plastic sleeve: 0.5 mm² ... 16 mm²
rigid (AWG): 20 ... 6 (Cu)
Stripping length: 10 mm
Tightening torque: 1.2 Nm ... 1.5 Nm
10 lbf-in. ... 13 lbf-in.
Drive form screw head: Slotted L
Signal
Position: 3.x
Identification: 3.1 (13), 3.2 (14)
Conductor connectionâۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Connection method: Screw connection
rigid: 0.5 mm² ... 16 mm²
flexible: 0.5 mm² ... 16 mm²
flexible with ferrule without plastic sleeve: 0.5 mm² ... 16 mm²
flexible with ferrule with plastic sleeve: 0.5 mm² ... 16 mm²
rigid (AWG): 20 ... 6 (Cu)
Stripping length: 10 mm
Tightening torque: 1.2 Nm ... 1.5 Nm
10 lbf-in. ... 13 lbf-in.
Drive form screw head: Slotted L
SignalingLED signaling
Types of signaling: LED DC OK âۉ€œ signal state operation (UN = 24 V DC, IOut = IN)
Function: Visual operating state display
Color: green
LED off: Supply voltage input AC not present (Off)
LED on (green), DC OK: UOUT > 0,9 x UN (On (green), DC OK)
LED on (flashing green) DC OK < 0.9 x UN: UOUT < 0,9 x UN (on (flashing green))
Electrical propertiesNumber of phases: 1.00
Insulation voltage input/output: 4 kV AC (type test)
3 kV AC (routine test)
Insulation voltage input / PE: 3.5 kV AC (type test)
2.4 kV AC (routine test)
Product propertiesProduct type: Power supply
Product family: UNO POWER
MTBF (IEC 61709, SN 29500): > 900000 h (25 °C)
> 530000 h (40 °C)
> 280000 h (55 °C)
Environmental protection directive: RoHS Directive 2011/65/EU
WEEE
Reach
Data management status
Article revision: 01
Insulation characteristics
Protection class: I
Degree of pollution: 2
DimensionsItem dimensions
Width: 126 mm
Height: 130 mm
Depth: 129 mm
125 mm (Device depth (DIN rail mounting))
Installation dimensions
Installation distance right/left (active, passive): 0 mm / 0 mm
Installation distance top/bottom (active, passive): 30 mm / 30 mm
MountingMounting type: DIN rail mounting
Assembly note: alignable: 0 mm horizontally, 30 mm vertically
Mounting position: horizontal DIN rail NS 35, EN 60715
With protective coating: no
Material specificationsFlammability rating according to UL 94: V0 (Housing, terminal blocks)
Housing material: Metal
Aluminum (AlMg3) / sheet steel, zinc-plated
Hood version: Stainless steel
Side element version: Aluminum
Foot latch material: Sheet steel, zinc-plated
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -25 °C ... 70 °C (> 55 °C Derating: 2.5 %/K)
Ambient temperature (storage/transport): -40 °C ... 85 °C
Ambient temperature (start-up type tested): -40 °C
Maximum altitude: ≤ 3000 m (> 2000 m, Derating: 10 %/1000 m)
Max. permissible relative humidity (operation): ≤ 95 % (at 25 °C, non-condensing)
Shock (operation): 18 ms, 30g, per spatial direction (IEC 60068-2-27)
Vibration (operation): < 13.2 Hz, amplitude ±1.0 mm (according to IEC 60068-2-6)
5 Hz ... 100 Hz, 0.7g (EN 60068-2-6)
Temp code: T4 (-25 °C ... +70 °C; >55 °C, derating: 2.5 %/K)
Standards and regulationsOvervoltage category
EN 61010-1: II (≤ 3000 m)
Overvoltage categoryâۉ€¹
EN 62477-1: III (≤3000 m)
Safety of power supply units up to 1100 V (insulation distances)
Standard designation: Safety of power supply units up to 1100 V (insulation distances)
Standards/specifications: DIN EN 61558-2-16
Electrical safety
Standard designation: Electrical safety
Standards/specifications: IEC 61010-2-201 (SELV)
Electronic equipment for use in power installations
Standard designation: Equipping high voltage installations with electronic equipment
Standards/specifications: EN 50178/VDE 0160 (PELV)
Safety for measurement, control, and laboratory equipment
Standard designation: Safety for equipment for measurement, control, and laboratory use
Standards/specifications: IEC 61010-1
Protective extra-low voltage
Standard designation: Protective extra-low voltage
Standards/specifications: IEC 61010-1 (SELV)
IEC 61010-2-201 (PELV)
Safe isolation
Standard designation: Safe isolation
Standards/specifications: IEC 61558-2-16
IEC 61010-2-201
Limitation of harmonic line currents
Standard designation: Limitation of harmonic line currents
Standards/specifications: EN 61000-3-2
Mains voltage dips
Standard designation: Requirement of the semiconductor industry with regard to mains voltage dips
Standards/specifications: SEMI F47 - 0706 (180 V AC)
ApprovalsUL
Identification: UL/C-UL Listed UL 61010-1
ULâۉ€¹
Identification: UL/C-UL Listed UL 61010-2-201
ULâۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Identification: UL/C-UL Listed ANSI/UL 121201 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
SIQ
Identification: CB scheme (IEC 61010-1, IEC 61010-2-201)
EMC dataElectromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
Low Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC
Interference emission: Interference emission in accordance with EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial)
EMC requirements for noise immunity: EN 61000-6-2
Conducted noise emission: EN 55016
EN 61000-6-3 (Class B)
Noise emission: EN 55016
EN 61000-6-3 (Class B)
Harmonic currents
Standards/regulations: EN 61000-3-2
EN 61000-3-2 (Class A)
Frequency range: 0 kHz ... 2 kHz
Flicker
Standards/regulations: EN 61000-3-3
Frequency range: 0 kHz ... 2 kHz
Electrostatic discharge
Standards/regulations: EN 61000-4-2
Electrostatic dischargeâۉ€¹
Contact discharge: 6 kV (Test Level 3)
Discharge in air: 8 kV (Test Level 3)
Comments: Criterion A
Electromagnetic HF field
Standards/regulations: EN 61000-4-3
Electromagnetic HF fieldâۉ€¹
Frequency range: 80 MHz ... 1 GHz
1 GHz ... 6 GHz
Test field strength: 10 V/m (Test Level 3)
Comments: Criterion A
Fast transients (burst)
Standards/regulations: EN 61000-4-4
Fast transients (burst)âۉ€¹
Input: 4 kV (Test Level 4 - asymmetrical)
Output: 2 kV (Test Level 3 - asymmetrical)
Comments: Criterion A
Surge voltage load (surge)
Standards/regulations: EN 61000-4-5
Surge voltage load (surge)âۉ€¹
Input: 1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Output: 0.5 kV (Test Level 2 - symmetrical)
1 kV (Test Level 2 - asymmetrical)
Comments: Criterion B
Conducted interference
Standards/regulations: EN 61000-4-6
Conducted interferenceâۉ€¹
Input/Output: asymmetrical
Frequency range: 0.15 MHz ... 80 MHz
Comments: Criterion A
Voltage: 10 V (Test Level 3)
Voltage dips
Standards/regulations: EN 61000-4-11
Voltage: 230 V AC
Frequency: 50 Hz
Voltage dip: 70 %
40 %
0 %
Number of periods: 25 / 30 periods
12 periods
1 period
Comments: Criterion A
Criterion B
Additional text: Test Level 2
Criteria
Criterion A: Normal operating behavior within the specified limits.
Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
Descrizione
UNO2-PS/1AC/24DC/960W Alimentatore