PHOENIX CONTACT 1234308
PHOENIX CONTACT 1234308
PHOENIX CONTACTNon disponibile

PS-EE-2G/1AC/24DC/480W/SC - Power supply unit

Primary-switched power supply unit, ESSENTIAL POWER, Screw connection, DIN rail mounting, input: 1-phase, output: 24 V DC / 20 A, adjustable from 24 V DC ... 28 V DC
Cod. Articolo: 1234308 copia - copy
Cod. Fornitore: 1234308 copia - copy
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Descrizione
Download
Caratteristiche Tecniche
Input dataAC operation
Supply system configuration: TN, TT, IT (PE)
Nominal input voltage range: 100 V AC ... 240 V AC
Input voltage range: 110 V AC ... 240 V AC ±10 % (PN = 480 W)
100 V AC ... 109 V AC -15 % ... +10 % (PN = 400 W)
Typical national grid voltage: 120 V AC
230 V AC
Voltage type of supply voltage: AC
Inrush current: typ. 16 A (at 25 °C)
Inrush current integral (I2t): typ. 0.25 A2s
Frequency range (fN): 50 Hz ... 60 Hz ±10 %
Mains buffering time: typ. 15 ms (120 V AC)
typ. 35 ms (230 V AC)
Current consumption: max. 6 A (480 W)
max. 5 A (400 W)
typ. 5 A (110 V AC (480 W))
typ. 2.3 A (240 V AC (480 W))
typ. 4.5 A (100 V AC (400 W))
typ. 4.3 A (109 V AC (400 W))
Protective circuit: Transient protection; Varistor
Switch-on time: typ. 1 s
Device mains fuse: 10 A internal (device protection), fast-blow
Recommended breaker for input protection: 6 A ... 16 A (Characteristic B, C, D, K or comparable)
Discharge current to PE: < 3.5 mA
Output dataEfficiency: typ. 91 % (120 V AC)
typ. 93 % (230 V AC)
Nominal output voltage: 24 V DC
Setting range of the output voltage (USet): 24 V DC ... 28 V DC (> 24 V DC, constant capacity restricted)
Nominal output current (IN): max. 20 A (PN = 480 W)
max. 16.66 A (PN = 400 W)
Short-circuit-proof: yes
No-load proof: yes
Crest factor: typ. 1,7 (120 V AC)
typ. 1.8 (230 V AC)
Output power (PN): 480 W (240 V AC)
400 W (100 V AC)
Connection in parallel: yes, for increasing power and redundancy with diode
Connection in series: yes, for increased output voltage
Feedback voltage resistance: ≤ 35 V DC
Protection against overvoltage at the output (OVP): ≤ 35 V DC
Residual ripple: typ. 70 mVPP (with nominal values)
Control deviation: < 2 % (change in load, static 10 % ... 90 %)
< 4 % (change in load, dynamic 10 % ... 90 %)
< 0.1 % (change in input voltage ±10 %)
Rise time: < 100 ms (UOut = 10 % ... 90 %)
Minimum no-load power dissipation: < 4 W (120 V AC)
Maximum no-load power dissipation: < 3 W (230 V AC)
Minimum nominal load power dissipation: < 43 W (120 V AC)
Power loss nominal load max.: < 33 W (230 V AC)
Integrated fuse protection: no
Connection dataInput
Position: 1.x
Identification: 1.1 (), 1.2 (L), 1.3 (N)
Conductor connection
Connection method: Screw connection
rigid: 0.75 mm² ... 6 mm²
flexible: 0.75 mm² ... 4 mm²
flexible with ferrule without plastic sleeve: 0.75 mm² ... 4 mm²
flexible with ferrule with plastic sleeve: 0.75 mm² ... 4 mm²
rigid (AWG): 18 ... 10 (Cu)
Stripping length: 8 mm
Tightening torque: 0.5 Nm ... 0.6 Nm
5 lbf-in. ... 7 lbf-in.
Drive form screw head: Slotted L
Output
Position: 2.x
Identification: 2.1, 2.2 (+), 2.3, 2.4 (-)
Conductor connectionâۉ€¹
Connection method: Screw connection
rigid: 2.5 mm² ... 6 mm²
flexible: 2.5 mm² ... 4 mm²
flexible with ferrule without plastic sleeve: 2.5 mm² ... 4 mm²
flexible with ferrule with plastic sleeve: 2.5 mm² ... 4 mm²
rigid (AWG): 14 ... 10 (Cu)
Stripping length: 6.5 mm
Tightening torque: 0.5 Nm ... 0.6 Nm
5 lbf-in. ... 7 lbf-in.
Drive form screw head: Slotted L
SignalingLED signaling
Types of signaling: LED DC OK âۉ€œ signal state operation (UN = 24 V DC, IOut = IN)
Function: Visual operating state display
Color: green
LED off: Supply voltage input AC not present (Off)
LED on (green), DC OK: UOUT > 11 V (On (green), DC OK)
Electrical propertiesNumber of phases: 1.00
Insulation voltage input/output: 4 kV AC (type test)
3 kV AC (routine test)
Insulation voltage input / PE: 3.5 kV AC (type test)
2.4 kV AC (routine test)
Product propertiesProduct type: Power supply
Product family: ESSENTIAL POWER
MTBF (Telcordia SR-332): > 860000 h (25 °C)
> 640000 h (40 °C)
> 570000 h (45 °C)
Data management status
Article revision: 02
Insulation characteristics
Protection class: I
Degree of pollution: 2
Life expectancy (electrolytic capacitors)
Current: 20 A
Temperature: 40 °C
Time: 25000 h
Additional text: 120 V AC
Life expectancy (electrolytic capacitors)âۉ€¹
Current: 20 A
Temperature: 30 °C
Time: 50000 h
Additional text: 120 V AC
Life expectancy (electrolytic capacitors)âۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Current: 20 A
Temperature: 40 °C
Time: 37000 h
Additional text: 230 V AC
Life expectancy (electrolytic capacitors)âۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Current: 20 A
Temperature: 30 °C
Time: 74000 h
Additional text: 230 V AC
DimensionsItem dimensions
Width: 86 mm
Height: 124 mm
Depth: 125 mm
Installation dimensions
Installation distance right/left: 10 mm / 10 mm
Installation distance top/bottom: 30 mm / 30 mm
MountingMounting type: DIN rail mounting
Assembly note: alignable: 0 mm horizontally, 30 mm vertically
Mounting position: horizontal DIN rail NS 35, EN 60715
With protective coating: no
Material specificationsHousing material: Metal
Aluminum (AlMg3) / sheet steel, zinc-plated
Hood version: Stainless steel
Side element version: Aluminum
Foot latch material: Sheet steel, zinc-plated
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -20 °C ... 70 °C (Derating >45 °C: 2.5%/K)
Ambient temperature (storage/transport): -40 °C ... 85 °C
Maximum altitude: ≤ 3000 m (> 2000 m, Derating: 10 %/1000 m)
Climatic class: 3K22 (in accordance with EN 60721-3-3)
Max. permissible relative humidity (operation): ≤ 95 % (at 25 °C, non-condensing)
Shock (operation): 15 ms, 15g, per spatial direction (IEC 60068-2-27)
Vibration (operation): 10 Hz ... 50 Hz, amplitude ±0.2 mm
50 Hz ... 150 Hz, 2.3g, 90 min.
Temp code: T4 (-20...+70 °C; >45 °C, Derating: 2,5 %/K)
Standards and regulationsOvervoltage category
EN 61010-1: II (≤ 3000 m)
Electrical safety
Standard designation: Electrical safety
Standards/specifications: IEC 61010-2-201 (SELV)
Safety for measurement, control, and laboratory equipment
Standard designation: Safety for equipment for measurement, control, and laboratory use
Standards/specifications: IEC 61010-1
Protective extra-low voltage
Standard designation: Protective extra-low voltage
Standards/specifications: IEC 61010-1 (SELV)
IEC 61010-2-201 (PELV)
Limitation of harmonic line currents
Standard designation: Limitation of harmonic line currents
Standards/specifications: EN 61000-3-2
Mains voltage dips
Standard designation: Requirement of the semiconductor industry with regard to mains voltage dips
Standards/specifications: SEMI F47 - 0706 (120 V AC)
Safe isolation
Standard designation: Safe isolation
Standards/specifications: IEC 61558-2-16
Note: Transformer
ApprovalsUL
Identification: UL/C-UL Listed UL 61010-1
ULâۉ€¹
Identification: UL/C-UL Listed UL 61010-2-201
CB scheme
Identification: CB scheme (IEC 61010-1, IEC 61010-2-201)
EMC dataElectromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
Low Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC
Interference emission: Interference emission in accordance with EN 61000-6-3 (residential and commercial) and EN 61000-6-4 (industrial)
EMC requirements for noise immunity: EN 61000-6-2
Conducted noise emission: EN 55016
EN 61000-6-3 (Class B)
Noise emission: EN 55016
EN 61000-6-3 (Class B)
Harmonic currents
Standards/regulations: EN 61000-3-2
EN 61000-3-2 (Class A)
Frequency range: 0 kHz ... 2 kHz
Electrostatic discharge
Standards/regulations: EN 61000-4-2
Electrostatic dischargeâۉ€¹
Contact discharge: 6 kV (Test Level 3)
Discharge in air: 8 kV (Test Level 3)
Comments: Criterion A
Electromagnetic HF field
Standards/regulations: EN 61000-4-3
Electromagnetic HF fieldâۉ€¹
Frequency range: 80 MHz ... 1 GHz
1 GHz ... 6 GHz
2 GHz ... 3 GHz
Test field strength: 10 V/m (Test Level 3)
1 V/m (Test Level 3)
Comments: Criterion A
Fast transients (burst)
Standards/regulations: EN 61000-4-4
Fast transients (burst)âۉ€¹
Input: 4 kV (Test Level 4 - asymmetrical)
Output: 2 kV (Test Level 3 - asymmetrical)
Comments: Criterion A
Surge voltage load (surge)
Standards/regulations: EN 61000-4-5
Surge voltage load (surge)âۉ€¹
Input: 1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Output: 0.5 kV (Test Level 2 - symmetrical)
1 kV (Test Level 2 - asymmetrical)
Comments: Criterion B
Conducted interference
Standards/regulations: EN 61000-4-6
Conducted interferenceâۉ€¹
Input/Output: asymmetrical
Frequency range: 0.15 MHz ... 80 MHz
Comments: Criterion A
Voltage: 10 V (Test Level 3)
Voltage dips
Standards/regulations: EN 61000-4-11
Voltage: 230 V AC
Frequency: 50 Hz
Voltage dip: 70 %
40 %
0 %
Number of periods: 25 periods
10 periods
1 period
Comments: Criterion A
Criteria
Criterion A: Normal operating behavior within the specified limits.
Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
Criterion C: Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
Descrizione
PS-EE-2G/1AC/24DC/480W/SC Alimentatore
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_01707.pdf

Data_sheet_01013.pdf

Manufacturer_declaration_04347.pdf

Manufacturer_declaration_05490.pdf

Package_slip_01809.pdf

Technical_drawing_10603.pdf