Input data | AC operation Nominal input voltage range: 3x 400 VÂAC ... 500 VÂAC Input voltage range: 3x 400 VÂAC ... 500 VÂAC -20Â%Â...Â+15Â% Voltage type of supply voltage: AC/DC Inrush current: < 15 A (at 25°C) Inrush current integral (I2t): < 1 A2s Inrush current limitation: 15 A AC frequency range: 45 Hz ... 65 Hz Frequency range DC: 0 Hz Mains buffering time: > 25 ms (400ÂVÂAC) > 35 ms (500 VÂAC) Current consumption: 3x 2.1 A (400ÂVÂAC) 3x 1.5 A (500 VÂAC) Nominal power consumption: 1342 VA Protective circuit: Transient surge protection; Varistor, gas-filled surge arrester Power factor (cos phi): 0.76 Typical response time: < 0.5 s Permissible backup fuse: B6 B10 B16 AC: Permissible DC backup fuse: DC: Connect a suitable fuse upstream Recommended breaker for input protection: 6 A ... 20 A (Characteristic B, C, D, K or comparable) Discharge current to PE: < 3.5 mA DC operation Nominal input voltage range: ± 500 VÂDC ... 600 VÂDC Input voltage range: 500 VÂDC ... 600 VÂDC -10Â%Â...Â+34Â% (mid-point earthed) Current consumption: 2.2 A (500ÂVÂDC) 1.9 A (600ÂVÂDC) Recommended breaker for input protection: 1x 6 A (10 x 38 mm, 30 kA L/R = 2 ms)
|
Output data | Efficiency: typ. 94 % (400ÂVÂAC) Output characteristic: U/I Nominal output voltage: 24 VÂDC ±1Â% Setting range of the output voltage (USet): 18 VÂDC ... 29.5 VÂDC (> 24 VÂDC, constant capacity restricted) Nominal output current (IN): 40 A POWER BOOST (IBoost): 45 A (-25°CÂ...Â40°C permanent, UOUT = 24ÂVÂDC ) Static Boost (IStat.Boost): 45 A Selective Fuse Breaking (ISFB): 215 A (12Âms) Magnetic circuit breaker tripping: B2 / B4 / B6 / B10 / B16 / B25 / C2 / C4 / C6 / C13 Derating: 60°C ... 70°C (2.5%/K) Feedback voltage resistance: ≤ 35 VÂDC Protection against overvoltage at the output (OVP): ≤ 35 VÂDC Control deviation: < 1 % (change in load, static 10 % ... 90 %) < 3 % (change in load, dynamic 10 % ... 90 %) < 0.1 % (change in input voltage ±10 %) Residual ripple: < 40 mVPP (with nominal values) Short-circuit-proof: yes Output power: 960 W 1080 W Peak switching voltages nominal load: < 5 mVPP (at nominal values, 20 MHz) Maximum no-load power dissipation: 18 W Power loss nominal load max.: 63 W Rise time: < 0.15 s (UOUT (10 % ... 90 %)) Connection in parallel: yes, for redundancy and increased capacity Connection in series: yes Signal: DC OK active Output description: UOUT > 0.9 x UN: High signal Switching voltage range: 18 VÂDC ... 24 VÂDC Output voltage: + 24 VÂDC Maximum inrush current: ≤ 20 mA (short-circuit-proof) Continuous load current: ≤ 20 mA Signal: DC OK floating Output description: Relay contact, UOUT > 0.9 x UN: Contact closed Maximum switching voltage: 30 V AC/DC 24 VÂDC Maximum inrush current: 0.5 A 1 A Continuous load current: ≤ 1 A Signal: POWER BOOST, active Output description: IOUT < IN: High signal Switching voltage range: 18 VÂDC ... 24 VÂDC Output voltage: + 24 VÂDC Maximum inrush current: ≤ 20 mA (short-circuit-proof) Continuous load current: ≤ 20 mA
|
Connection data | Input Connection method: Screw connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 6 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 4 mm² Conductor cross section AWG min.: 18 Conductor cross section AWG max.: 10 Stripping length: 7 mm Screw thread: M3 Tightening torque, min: 0.5 Nm Tightening torque max: 0.6 Nm Output Connection method: Screw connection Conductor cross section, rigid min.: 0.5 mm² Conductor cross section, rigid max.: 16 mm² Conductor cross section flexible min.: 0.5 mm² Conductor cross section flexible max.: 16 mm² Conductor cross section AWG min.: 8 Conductor cross section AWG max.: 6 Stripping length: 10 mm Screw thread: M4 Tightening torque, min: 1.2 Nm Tightening torque max: 1.5 Nm Signal Connection method: Screw connection Conductor cross section, rigid min.: 0.2 mm² Conductor cross section, rigid max.: 6 mm² Conductor cross section flexible min.: 0.2 mm² Conductor cross section flexible max.: 4 mm² Conductor cross section AWG min.: 18 Conductor cross section AWG max.: 10 Screw thread: M3 Tightening torque, min: 0.5 Nm Tightening torque max: 0.6 Nm
|
Signaling | Types of signaling: LED Active switching output Relay contact Operating voltage display: Green LED Signal output: DC OK active Status display: UOUT > 0.9 x UN: "DC OK" LED green Note on status display: UOUT < 0.9 x UN: Flashing "DC OK" LED Signal output: DC OK floating Status display: UOUT > 0.9 x UN: "DC OK" LED green Note on status display: UOUT < 0.9 x UN: Flashing "DC OK" LED Signal output: POWER BOOST, active Status display: IOUT > IN: LED "BOOST" yellow
|
Electrical properties | Number of phases: 3.00 Insulation voltage input/output: 4 kV AC (type test) 2 kV AC (routine test) Insulation voltage output / PE: 500 VÂDC (routine test) Insulation voltage input / PE: 3.5 kV AC (type test) 2 kV AC (routine test)
|
Product properties | Product type: Power supply Product family: QUINT POWER MTBF (IEC 61709, SN 29500): > 880000 h (25°C) > 500000 h (40°C) > 216000 h (60°C) Insulation characteristics Protection class: I Degree of pollution: 2
|
Dimensions | Width: 96 mm Height: 130 mm Depth: 176 mm Installation dimensions Installation distance right/left: 5 mm / 5 mm Installation distance top/bottom: 50 mm / 50 mm Alternative assembly Width: 176 mm Height: 130 mm Depth: 99 mm
|
Mounting | Mounting type: DIN rail mounting Assembly instructions: alignable: PN ≥50%, 5Âmm horizontally, 15Âmm next to active components, 50Âmm vertically alignable: PN <50%, 0Âmm horizontally, 40Âmm vertically top, 20 mm vertically bottom Mounting position: horizontal DIN rail NS 35, EN 60715 With protective coating: No
|
Material specifications | Housing material: Metal Hood version: Galvanized sheet steel, free from chrome (VI) Side element version: Aluminum
|
Environmental and real-life conditions | Ambient conditions Degree of protection: IP20 Ambient temperature (operation): -25°C ... 70°C (>Â60°C Derating: 2,5Â%/K) Ambient temperature (storage/transport): -40°C ... 85°C Ambient temperature (start-up type tested): -40°C Maximum altitude: 5000 m Climatic class: 3K3 (in acc. with EN 60721) Max. permissible relative humidity (operation): ≤ 95 % (at 25°C, non-condensing) Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27) Vibration (operation): 5ÂHz ... 100ÂHz resonance search 0.7g, 90Âmin., resonance frequency 0.7g, 90Âmin. (in accordance with DNV GL Class A)
|
Standards and regulations | Rail applications: ENÂ50121-4 ENÂ50121-3-2 Standard âۉ€œ Limitation of mains harmonic currents: ENÂ61000-3-2 Standard - Electrical safety: IEC 61010-2-201Â(SELV) Standard - Equipment safety: GS (tested safety) Standard âۉ€œ Safety extra-low voltage: IEC 61010-1 (SELV) IEC 61010-2-201 (PELV) Standard - Safe isolation: IEC 61010-2-201 Standard - safety for equipment for measurement, control, and laboratory use: IEC 61010-1 Standard - surge resistance: VDEÂ0160 (curve W2) Overvoltage category EN 61010-1: IIÂ(≤Â5000Âm) EN 62477-1: IIIÂ(≤Â2000Âm) ENÂ61558-2-16: IIÂ(≤Â4000Âm)
|
Approvals | CSA: CAN/CSA-C22.2 No.Â60950-1-07 CSA-C22.2 No.Â107.1-01 Shipbuilding approval: DNV GL (EMC A), ABS, LR, RINA, NK, BV UL approvals: UL Listed ULÂ508 UL/C-UL Recognized ULÂ60950-1 (3-wire + PE, star net) UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
|
EMC data | Low Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC EMC requirements for noise emission: ENÂ61000-6-3 ENÂ61000-6-4 EMC requirements for noise immunity: ENÂ61000-6-1 ENÂ61000-6-2 Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU Electrostatic discharge Standards/regulations: ENÂ61000-4-2 Electrostatic dischargeâۉ€¹ Contact discharge: 8 kV (Test Level 4) Discharge in air: 15 kV (Test Level 4) Comments: Criterion A Electromagnetic HF field Standards/regulations: ENÂ61000-4-3 Electromagnetic HF fieldâۉ€¹ Frequency range: 80 MHz ... 1 GHz 1 GHz ... 2 GHz 2 GHz ... 3 GHz Test field strength: 20 V/m (Test Level 3) 10 V/m (Test Level 3) 10 V/m (Test Level 3) Comments: Criterion A Fast transients (burst) Standards/regulations: ENÂ61000-4-4 Fast transients (burst)âۉ€¹ Input: 4 kV (Test Level 4 - asymmetrical) Output: 2 kV (Test Level 3 - asymmetrical) Signal: 2 kV (Test Level 4 - asymmetrical) Comments: Criterion A Surge voltage load (surge) Standards/regulations: ENÂ61000-4-5 Input: 2 kV (Test Level 3 - symmetrical) 6 kV (Test Level 4 - asymmetrical) Output: 1 kV (Test Level 2 - symmetrical) 2 kV (Test Level 3 - asymmetrical) Signal: 1 kV (Test Level 2 - asymmetrical) Comments: Criterion A Conducted interference Standards/regulations: ENÂ61000-4-6 Conducted interferenceâۉ€¹ I/O/S: asymmetrical Frequency range: 0.15 MHz ... 80 MHz Comments: Criterion A Voltage: 10 V (Test Level 3) Emitted interference Standards/regulations: ENÂ61000-6-3 Radio interference voltage in acc. with EN 55011: ENÂ55011 (ENÂ55022) ClassÂB, area of application: Industry and residential Emitted radio interference in acc. with EN 55011: EN 55011 (EN 55022) Class B, area of application: Industry and residential Criteria Criterion A: Normal operating behavior within the specified limits. Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
|