Automazione Industriale

Meccatroinca

Meccatronica

Sicurezza Industriale

Componenti Quadri

Sensori e Sistemi di Visione

Pneumatica

Network e Comunicazione

Cavi Speciali

Accedi ai servizi

Entra nella tua area riservata

Accedi ai servizi

Entra nella tua area riservata

PHOENIX CONTACT 2903154
PHOENIX CONTACT 2903154
PHOENIX CONTACTDisponibile

TRIO-PS-2G/3AC/24DC/10 - Power supply unit

Primary-switched TRIO POWER power supply with push-in connection for DIN rail mounting, input: 3-phase, output: 24VDC/10A
Cod. Articolo: 2903154 copia - copy
Cod. Fornitore: 2903154 copia - copy
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Download
Caratteristiche Tecniche
Input dataAC operation
Network type: Star network
Nominal input voltage range: 3x 400 VÂAC ... 500 VÂAC
2x 400 VÂAC ... 500 VÂAC
Input voltage range: 3x 400 VÂAC ... 500 VÂAC -20Â%Â...Â+15Â%
2x 400 VÂAC ... 500 VÂAC -10Â%Â...Â+15Â%
Input voltage range AC: 3x 320 VÂAC ... 575 VÂAC
Typical national grid voltage: 3x 400 VÂAC
3x 480 VÂAC
Voltage type of supply voltage: AC
Inrush current: ≤ 26 A (typical)
Inrush current integral (I2t): ≤ 0.3 A2s
AC frequency range: 50 Hz ... 60 Hz
Mains buffering time: typ. 10 ms (400ÂVÂAC)
typ. 20 ms (500 VÂAC)
Current consumption: 3x 0.6 A (400ÂVÂAC)
3x 0.6 A (500 VÂAC)
2x 1.1 A (400ÂVÂAC)
2x 1.1 A (500 VÂAC)
Nominal power consumption: 451.7 VA
Protective circuit: Transient surge protection; Varistor
Power factor (cos phi): 0.58
Typical response time: < 1 s
Input fuse: 3.15 A (internal (device protection), slow-blow)
Recommended breaker for input protection: 6 A ... 16 A (Characteristics B, C, D, K)
Discharge current to PE: < 3.5 mA
< (550 V AC, 60 Hz)
Output dataEfficiency: > 92 % (at 400 V AC and nominal values)
Output characteristic: U/I with dynamic load reserve
Nominal output voltage: 24 VÂDC ±1Â%
Setting range of the output voltage (USet): 24 VÂDC ... 28 VÂDC (> 24 VÂDC, constant capacity restricted)
Nominal output current (IN): 10 A
Dynamic Boost (IDyn.Boost): 15 A (5 s)
Derating: > 60°C ... 70°C (2.5%/K)
Protection against overvoltage at the output (OVP): ≤ 30 VÂDC
Control deviation: < 1 % (change in load, static 10 % ... 90 %)
< 3 % (Dynamic load change 10 % ... 90 %, 10 Hz)
< 0.1 % (change in input voltage ±10 %)
Residual ripple: ≤ 20 mVPP
Short-circuit-proof: yes
No-load proof: yes
Output power: 240 W
360 W
Maximum no-load power dissipation: < 1.1 W (400ÂVÂAC)
Power loss nominal load max.: < 22 W (480ÂVÂAC)
Rise time: ≤ 120 ms (UOUT (10 % ... 90 %))
Connection in parallel: yes, for redundancy and increased capacity
Connection in series: yes
Signal: DC OK
Continuous load current: 100 mA
Signal relay 13/14
Default: closed
Digital: 30 VÂAC 30 VÂDC 100 mA
Connection dataInput
Connection method: Push-in connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 4 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Single conductor/terminal point, stranded, with ferrule, min.: 0.2 mm²
Single conductor/terminal point, stranded, with ferrule, max.: 2.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 12
Stripping length: 10 mm
Output
Connection method: Push-in connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 4 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Single conductor/terminal point, stranded, with ferrule, min.: 0.2 mm²
Single conductor/terminal point, stranded, with ferrule, max.: 2.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 12
Stripping length: 10 mm
Signal
Connection method: Push-in connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 1.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 1.5 mm²
Single conductor/terminal point, stranded, with ferrule, min.: 0.2 mm²
Single conductor/terminal point, stranded, with ferrule, max.: 1.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 16
Stripping length: 8 mm
SignalingTypes of signaling: LED
Floating signal contact
Signal output: LED status indicator
Signalization designation: DC OK
Status display: LED
Color: green
DC OK: UOUT > 0.9 x UN (UN = 24ÂVÂDC)
Electrical propertiesNumber of phases: 3.00
Insulation voltage input/output: 3 kV AC (type test)
1.5 kV AC (routine test)
Product propertiesProduct type: Power supply
Product family: TRIO POWER
MTBF (IEC 61709, SN 29500): > 2100000 h (25°C)
> 1200000 h (40°C)
> 590000 h (60°C)
Insulation characteristics
Protection class: I (in closed control cabinet)
Degree of pollution: 2
DimensionsWidth: 42 mm
Height: 130 mm
Depth: 160 mm
Installation dimensions
Installation distance right/left: 0 mm / 0 mm
Installation distance top/bottom: 50 mm / 50 mm
MountingMounting type: DIN rail mounting
Assembly instructions: alignable: horizontally 0 mm (≤ 40°C) 10 mm (≤ 70°C), vertically 50 mm
Mounting position: horizontal DIN rail NS 35, EN 60715
With protective coating: No
Material specificationsFlammability rating according to ULÂ94 (housing / terminal blocks): V0
Housing material: Metal
Type of housing: Aluminum (AlMg3)
Hood version: Polycarbonate
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -25°C ... 70°C (>Â60°C Derating: 2,5Â%/K)
Ambient temperature (storage/transport): -40°C ... 85°C
Ambient temperature (start-up type tested): -40°C
Maximum altitude: ≤ 5000 m (>Â2000Âm, Derating: 10Â%/1000Âm)
Climatic class: 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation): ≤ 95 % (at 25°C, non-condensing)
Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation): < 15 Hz, amplitude ±2.5 mm (according to IEC 60068-2-6)
15 Hz ... 150 Hz, 4g, 90 min.
Standards and regulationsRail applications: ENÂ50121-4
Standard âۉ€œ Electronic equipment for use in electrical power installations and their assembly into electrical power installations: ENÂ50178/VDEÂ0160 (PELV)
Standard âۉ€œ Limitation of mains harmonic currents: ENÂ61000-3-2
Standard - Electrical safety: IEC 62368-1Â(SELV)
Standard âۉ€œ Safety extra-low voltage: IEC 62368-1 (SELV) und ENÂ60204-1 (PELV)
Standard - Safe isolation: DINÂVDEÂ0100-410
Standard - Safety of transformers: ENÂ61558-2-16 (air clearances and creepage distances only)
ApprovalsUL approvals: UL Listed ULÂ508
UL/C-UL Recognized ULÂ60950-1
Conformity/Approvals
SIL in accordance with IEC 61508: 0
EMC dataLow Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emission: ENÂ61000-6-3
ENÂ61000-6-4
EMC requirements for noise immunity: ENÂ61000-6-1
ENÂ61000-6-2
Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
Conducted noise emission: ENÂ55016
ENÂ61000-6-3 (Class B)
Noise emission: EN 55011 (EN 55022)
Electrostatic discharge
Standards/regulations: ENÂ61000-4-2
Electrostatic dischargeâۉ€¹
Contact discharge: 6 kV (Test Level 4)
Discharge in air: 8 kV (Test Level 4)
Comments: Criterion A
Electromagnetic HF field
Standards/regulations: ENÂ61000-4-3
Electromagnetic HF fieldâۉ€¹
Frequency range: 80 MHz ... 1 GHz
1 GHz ... 2 GHz
2 GHz ... 3 GHz
Test field strength: 10 V/m (Test Level 3)
Comments: Criterion A
Fast transients (burst)
Standards/regulations: ENÂ61000-4-4
Fast transients (burst)âۉ€¹
Input: 4 kV (Test Level 4 - asymmetrical)
Output: 2 kV (Test Level 3 - asymmetrical)
Signal: 1 kV (Test Level 2 - asymmetrical)
Comments: Criterion A
Surge voltage load (surge)
Standards/regulations: ENÂ61000-4-5
Input: 3 kV (Test Level 3 - symmetrical)
6 kV (Test Level 4 - asymmetrical)
Output: 1 kV (Test Level 2 - symmetrical)
2 kV (Test Level 1 - asymmetrical)
Signal: 1 kV (Test Level 1 - symmetrical)
Comments: Criterion B
Conducted interference
Standards/regulations: ENÂ61000-4-6
Conducted interferenceâۉ€¹
Input/Output: asymmetrical
Frequency range: 0.15 MHz ... 80 MHz
Comments: Criterion A
Voltage: 10 V (Test Level 3)
Emitted interference
Standards/regulations: ENÂ61000-6-3
Radio interference voltage in acc. with EN 55011: ENÂ55011 (ENÂ55022) ClassÂB, area of application: Industry and residential
Emitted radio interference in acc. with EN 55011: EN 55011 (EN 55022) Class B, area of application: Industry and residential
Criteria
Criterion A: Normal operating behavior within the specified limits.
Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00040.pdf

Approvals_00041.pdf

Approvals_00054.pdf

Approvals_00055.pdf

Approvals_00056.pdf

Approvals_00057.pdf

Approvals_01301.pdf

Data_sheet_03804.pdf

Manufacturer_declaration_03074.pdf

Manufacturer_declaration_04785.pdf

Manufacturer_declaration_05508.pdf

Manufacturer_declaration_15780.pdf

Package_slip_02453.pdf

Technical_drawing_39712.pdf

Various_00006.pdf