PHOENIX CONTACT 2904595
PHOENIX CONTACT 2904595
PHOENIX CONTACTNon disponibile

QUINT4-PS/1AC/5DC/5/PT - Power supply unit

Primary-switched power supply unit QUINT POWER, Push-in connection, DIN rail mounting, input:1-phase, output: 5 VDC / 5 A
Cod. Articolo: 2904595 copia - copy
Cod. Fornitore: 2904595 copia - copy
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Download
Caratteristiche Tecniche
Input dataAC operation
Input voltage range: 100 VÂAC ... 240 VÂAC -15Â%Â...Â+10Â%
Electric strength, max.: 300 VÂAC (60 s)
Typical national grid voltage: 120 VÂAC
230 VÂAC
Voltage type of supply voltage: AC/DC
Inrush current: typ. 9.1 A (at 25°C)
Inrush current integral (I2t): < 0.1 A2s
Inrush current limitation: < 9.1 A
Frequency range (fN): 50 Hz ... 60 Hz -10Â%Â...Â+10Â%
Mains buffering time: typ. 52 ms (120ÂVÂAC)
typ. 52 ms (230 V AC)
Current consumption: 0.37 A (100ÂVÂAC)
0.3 A (120ÂVÂAC)
0.17 A (230 V AC)
0.16 A (240ÂVÂAC)
Nominal power consumption: 32.8 VA
Protective circuit: Transient surge protection; Varistor
Typical response time: 350 ms
Input fuse: 3.15 A (slow-blow, internal)
Recommended breaker for input protection: 6 A ... 16 A (Characteristic B, C or comparable)
Discharge current to PE: < 0.25 mA (264ÂVÂAC, 60ÂHz)
typ. 0.08 mA
DC operation
Input voltage range: 110 VÂDC ... 250 VÂDC -20Â%Â...Â+40Â%
Voltage type of supply voltage: AC/DC
Current consumption: 0.32 A (110ÂVÂDC)
0.14 A (250ÂVÂDC)
Output dataEfficiency: typ. 87.4 % (120ÂVÂAC)
typ. 88.4 % (230 V AC)
Nominal output voltage: 5 VÂDC
Setting range of the output voltage (USet): 5 VÂDC ... 6.2 VÂDC (constant capacity)
Nominal output current (IN): 5 A
Static Boost (IStat.Boost): 6.25 A (≤Â40°C)
Dynamic Boost (IDyn.Boost): 8 A (≤Â60°C (5Âs))
Feedback voltage resistance: ≤ 16 VÂDC (16ÂV e-caps in output circuit)
Protection against overvoltage at the output (OVP): < 8 VÂDC
Control deviation: < 0.3 % (change in load, static 10 % ... 90 %)
< 3 % (DynamicÂloadÂchangeÂ10%Â...Â90%, 10ÂHzÂ<Â4%)
< 0.1 % (change in input voltage ±10 %)
Residual ripple: < 50 mVPP (with nominal values)
Short-circuit-proof: yes
No-load proof: yes
Output power: 25 W
31 W
40 W
Maximum no-load power dissipation: < 0.37 W (120ÂVÂAC)
< 0.41 W (230 V AC)
Power loss nominal load max.: < 3.7 W (120ÂVÂAC)
< 3.3 W (230 V AC)
Crest factor: typ. 1.88 (120ÂVÂAC)
typ. 2.09 (230 V AC)
Rise time: 50 ms (UOutÂ=Â10Â%Â...Â90Â%)
Connection in parallel: yes, for redundancy and increased capacity
Connection in series: yes
Signal (configurable)
Digital: 0 VÂDC 10 VÂDC 24 mA
Default: 10 VÂDC 24 mA 10ÂVÂDC for UOut >Â0.9ÂxÂUSet
Connection dataInput
Connection method: Push-in connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Single conductor/terminal point, stranded, with ferrule, min.: 0.25 mm²
Single conductor/terminal point, stranded, with ferrule, max.: 2.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 14
Stripping length: 10 mm
Output
Connection method: Push-in connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Single conductor/terminal point, stranded, with ferrule, min.: 0.25 mm²
Single conductor/terminal point, stranded, with ferrule, max.: 2.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 14
Stripping length: 10 mm
Signal
Connection method: Push-in connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Single conductor/terminal point, stranded, with ferrule, min.: 0.25 mm²
Single conductor/terminal point, stranded, with ferrule, max.: 2.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 14
Stripping length: 10 mm
SignalingTypes of signaling: LED
Signal output
POut: > PThr (LED lights up yellow, output power > PThr, depending on the rotary selector switch setting)
UOut: > 0.9ÂxÂUSet (LED lights up green)
< 0.9ÂxÂUSet (LED flashes green)
Electrical propertiesNumber of phases: 1.00
Insulation voltage input/output: 4 kV AC (type test)
3 kV AC (routine test)
Switching frequency: 75 kHz ... 220 kHz (Auxiliary converter stage)
4 kHz ... 70 kHz (Main converter stage)
30 kHz ... 135 kHz (PFC stage)
Product propertiesProduct type: Power supply
Product family: QUINT POWER
MTBF (IEC 61709, SN 29500): > 1890000 h (25°C)
> 1080700 h (40°C)
> 473300 h (60°C)
Insulation characteristics
Protection class: II
Degree of pollution: 2
Life expectancy (electrolytic capacitors)
Current: 2.5 A
Temperature: 40°C
Time: 91800 h
Additional text: 120ÂVÂAC
Life expectancy (electrolytic capacitors)âۉ€¹
Current: 2.5 A
Temperature: 40°C
Time: 98400 h
Additional text: 230ÂVÂAC
Life expectancy (electrolytic capacitors)âۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Current: 2.5 A
Temperature: 25°C
Time: 183400 h
Additional text: 120ÂVÂAC
Life expectancy (electrolytic capacitors)âۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Current: 2.5 A
Temperature: 25°C
Time: 186600 h
Additional text: 230ÂVÂAC
DimensionsWidth: 22.5 mm
Height: 106 mm
Depth: 90 mm
Installation dimensions
Installation distance right/left (active): 15 mm / 15 mm (POutÂ≥50%Â)
Installation distance right/left (passive): 5 mm / 5 mm (POutÂ≥50%Â)
Installation distance right/left (active, passive): 0 mm / 0 mm (POutÂ≤50Â%)
Installation distance top/bottom (active): 30 mm / 30 mm (POutÂ≥50%Â)
Installation distance top/bottom (passive): 30 mm / 30 mm (POutÂ≥50%Â)
Installation distance top/bottom (active, passive): 30 mm / 30 mm (POutÂ≤50Â%)
MountingMounting type: DIN rail mounting
With protective coating: No
Material specificationsFlammability rating according to ULÂ94 (housing / terminal blocks): V0
Housing material: Plastic
Type of housing: Polycarbonate
Hood version: Polycarbonate
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -25°C ... 70°C (>Â60°C Derating: 2,5Â%/K)
Ambient temperature (storage/transport): -40°C ... 85°C
Ambient temperature (start-up type tested): -40°C
Maximum altitude: ≤ 5000 m (> 2000 m, observe derating)
Climatic class: 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation): ≤ 95 % (at 25°C, non-condensing)
Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation): < 15ÂHz, ±2.5Âmm amplitude; 15ÂHz ... 100ÂHz: 2.3Âg 90ÂMin. (in accordance with IEC 60068-2-6)
Standards and regulationsRail applications: ENÂ50121-3-2
ENÂ50121-5
IEC 62236-3-2
IEC 62236-5
Standard âۉ€œ Limitation of mains harmonic currents: ENÂ61000-3-2
Standard - Electrical safety: IEC 61010-1 (SELV)
Standard âۉ€œ Safety extra-low voltage: IEC 61010-1 (SELV)
IEC 61010-2-201 (PELV)
Standard - Safe isolation: IEC 61558-2-16
Standard - safety for equipment for measurement, control, and laboratory use: IEC 61010-1
Standard - Safety of power supply units up to 1100 V (insulation distances): DINÂENÂ61558-2-16
Standard - Safety of transformers: ENÂ61558-2-16
Standard - power supply devices for low voltage with DC output: ENÂ61204-3
Overvoltage category
EN 61010-1: IIÂ(≤Â5000Âm)
EN 62477-1: IIIÂ(≤Â2000Âm)
ApprovalsSIQ: CB-Scheme (IEC 61010-1, IEC 61010-2-201)
UL approvals: UL Listed ULÂ61010-1
UL Listed ULÂ61010-2-201
UL 1310 Class 2 Power Units
Conformity/Approvals
SIL in accordance with IEC 61508: 0
EMC dataEMC requirements for noise emission: ENÂ61000-6-3
ENÂ61000-6-4
EMC requirements for noise immunity: ENÂ61000-6-1
ENÂ61000-6-2
Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
EMC requirements, power plant: IEC 61850-3
ENÂ61000-6-5
Conducted noise emission: ENÂ55016
ENÂ61000-6-3 (Class B)
Noise emission: Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply)
ENÂ55016
ENÂ61000-6-3 (Class B)
Harmonic currents
Standards/regulations: ENÂ61000-3-2
ENÂ61000-3-2 (Class A)
Frequency range: 0 kHz ... 2 kHz
Flicker
Standards/regulations: ENÂ61000-3-3
Frequency range: 0 kHz ... 2 kHz
Electrostatic discharge
Standards/regulations: ENÂ61000-4-2
Electrostatic dischargeâۉ€¹
Contact discharge: 8 kV (Test Level 4)
Discharge in air: 15 kV (Test Level 4)
Comments: Criterion A
Electromagnetic HF field
Standards/regulations: ENÂ61000-4-3
Electromagnetic HF fieldâۉ€¹
Frequency range: 80 MHz ... 1 GHz
1 GHz ... 6 GHz
Test field strength: 20 V/m (Test Level X)
10 V/m (Test Level 3)
Comments: Criterion A
Fast transients (burst)
Standards/regulations: ENÂ61000-4-4
Fast transients (burst)âۉ€¹
Input: 4 kV (Test Level 4 - asymmetrical)
Output: 4 kV (Test Level X - asymmetrical)
Signal: 4 kV (Test Level X - asymmetrical)
Comments: Criterion A
Surge voltage load (surge)
Standards/regulations: ENÂ61000-4-5
Input: 2 kV (Test Level 4 - symmetrical)
4 kV (Test Level 4 - asymmetrical)
Output: 1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Signal: 0.5 kV (Test Level 2 - symmetrical)
1 kV (Test Level 2 - asymmetrical)
Comments: Criterion A
Conducted interference
Standards/regulations: ENÂ61000-4-6
Conducted interferenceâۉ€¹
I/O/S: asymmetrical
Frequency range: 0.15 MHz ... 80 MHz
Comments: Criterion A
Voltage: 10 V (Test Level 3)
Power frequency magnetic field
Standards/regulations: ENÂ61000-4-8
Frequency: 16.67 Hz
50 Hz
60 Hz
50 Hz
60 Hz
0 Hz
Test field strength: 100 A/m
1 kA/m
300 A/m
Additional text: 60 s
3 s
DC, 60Âs
Comments: Criterion A
Frequency range: 50 Hz ... 60 Hz
Voltage dips
Standards/regulations: ENÂ61000-4-11
Voltage: 100 VÂAC
Frequency: 60 Hz
Voltage dip: 70 %
40 %
0 %
Number of periods: 1Â/Â25Â/Â30Âperiods
10Â/Â50Âperiods
0.5 / 1 / 5 / 50 periods
Additional text: Test Level 2
Comments: Criterion A
Criterion B
Pulse-shape magnetic field
Standards/regulations: ENÂ61000-4-9
Test field strength: 1000 A/m
Comments: Criterion A
Attenuated sinusoidal oscillations (ring wave)
Standards/regulations: ENÂ61000-4-12
Input: 2 kV (symmetrical)
4 kV (asymmetrical)
Comments: Criterion A
Asymmetrical conducted disturbance variables
Standards/regulations: ENÂ61000-4-16
Test level 1: 16.67 Hz 50 Hz 60 Hz 150 Hz 180 Hz (Test Level 3)
Voltage: 30 V (10Âs)
300 V (1 s)
Test level 2: 16.67 Hz 50 Hz 60 Hz (Test Level 2)
Comments: Criterion A
Attenuated oscillating wave
Standards/regulations: ENÂ61000-4-18
Voltage: 1 kV (symmetrical)
2.5 kV (asymmetrical)
1 kV (symmetrical)
Comments: Criterion A
Criteria
Criterion A: Normal operating behavior within the specified limits.
Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
Criterion C: Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_01297.pdf

Approvals_01335.pdf

Approvals_01401.pdf

Approvals_01402.pdf

Data_sheet_03829.pdf

Manufacturer_declaration_03160.pdf

Manufacturer_declaration_04799.pdf

Manufacturer_declaration_05498.pdf

Manufacturer_declaration_15939.pdf

Package_slip_02136.pdf

Product_information_00033.pdf

Product_information_00640.pdf

Technical_drawing_39968.pdf

Various_00006.pdf