QUINT4-PS/1AC/12DC/15 - Power supply unit

Primary-switched QUINT POWER power supply with free choice of output characteristic curve, SFB(Selective Fuse Breaking) Technology, and NFC interface, input: 1-phase, output: 12VDC/15 A
Cod. Articolo: 2904608 copia - copy
Cod. Fornitore: 2904608 copia - copy
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Download
Caratteristiche Tecniche
Input dataControl input (configurable) Rem: Output power ON/OFF (SLEEP MODE)
Default: Output power ON (>40ÂkΩ/24 V DC/open bridge between Rem and SGnd)
AC operation
Nominal input voltage range: 100 VÂAC ... 240 VÂAC
Input voltage range: 100 VÂAC ... 240 VÂAC -15Â%Â...Â+10Â%
Electric strength, max.: 300 VÂAC 60 s
Typical national grid voltage: 120 VÂAC
230 VÂAC
Voltage type of supply voltage: AC
Inrush current: typ. 15 A (at 25°C)
Inrush current integral (I2t): < 0.6 A2s
Inrush current limitation: 15 A (after 1Âms)
AC frequency range: 50 Hz ... 60 Hz -10Â%Â...Â+10Â%
Frequency range (fN): 50 Hz ... 60 Hz -10Â%Â...Â+10Â%
16.7 Hz (acc. to ENÂ50163)
Mains buffering time: typ. 55 ms (120ÂVÂAC)
typ. 56 ms (230 VÂAC)
Current consumption: 2.4 A (100ÂVÂAC)
1.9 A (120ÂVÂAC)
1.1 A (230 V AC)
1.1 A (240ÂVÂAC)
Nominal power consumption: 221 VA
Protective circuit: Transient surge protection; Varistor, gas-filled surge arrester
Switch-on time: < 1 s
Typical response time: 300 ms (from SLEEP MODE)
Input fuse: 8 A (slow-blow, internal)
Recommended breaker for input protection: 10 A ... 16 A (Characteristic B, C, D, K or comparable)
Discharge current to PE: < 3.5 mA
0.7 mA (264ÂVÂAC, 60ÂHz)
DC operation
Nominal input voltage range: 110 VÂDC ... 250 VÂDC
Input voltage range: 110 VÂDC ... 250 VÂDC -18Â%Â...Â+40Â%
Voltage type of supply voltage: DC
Current consumption: 2.2 A (110ÂVÂDC)
1 A (250ÂVÂDC)
Output dataEfficiency: typ. 91.2 % (120ÂVÂAC)
typ. 92 % (230 V AC)
Nominal output voltage: 12 VÂDC
Setting range of the output voltage (USet): 12 VÂDC ... 15 VÂDC (constant capacity)
Nominal output current (IN): 15 A
Static Boost (IStat.Boost): 17.5 A
Dynamic Boost (IDyn.Boost): 20 A (5 s)
Selective Fuse Breaking (ISFB): 60 A (15 ms)
Magnetic circuit breaker tripping: A1...A6 / B2...B6 / C1...C2 / Z1...Z6
Derating: > 60°C ... 70°C (2.5%/K)
Feedback voltage resistance: ≤ 25 VÂDC
Protection against overvoltage at the output (OVP): ≤ 18 VÂDC
Control deviation: < 0.5 % (Static load change 10Â% ... 90Â%)
< 4 % (Dynamic load change 10Â% ... 90Â%, (10 Hz))
< 0.25 % (change in input voltage ±10 %)
Residual ripple: < 70 mVPP (with nominal values)
Short-circuit-proof: yes
No-load proof: yes
Output power: 180 W
210 W
240 W
Apparent power: 660 VA (120ÂV, UOUT = 12ÂV, IOUT = stat. boost)
644 VA ()
Maximum no-load power dissipation: < 4 W (120ÂVÂAC)
< 4 W (230 V AC)
Power loss nominal load max.: < 18 W (120ÂVÂAC)
< 16 W (230 V AC)
Power dissipation SLEEP MODE: < 4 W (120ÂVÂAC)
< 4 W (230 V AC)
Crest factor: typ. 1.58 (120ÂVÂAC)
typ. 1.59 (230 V AC)
Rise time: < 1 s (UOutÂ=Â10Â%Â...Â90Â%)
Connection in parallel: yes, for redundancy and increased capacity
Connection in series: yes
Signal
Signal ground SGnd: Reference potential for Out1, Out2, and Rem
Signal Out 1 (configurable)
Digital: 24 VÂDC 20 mA
Default: 24 VÂDC 20 mA 24ÂVÂDC for UOut >Â0.9ÂxÂUSet
Signal Out 2 (configurable)
Digital: 24 VÂDC 20 mA
Analog: 4 mA ... 20 mA ±5Â% (Load ≤400ÂΩ)
Default: 24 VÂDC 20 mA 24ÂVÂDC for POutÂ<ÂPN
Signal relay 13/14 (configurable)
Default: closed (Uout > 0.9 USet)
Digital: 24 VÂDC 1 A
30 V AC/DC 0.5 A
Connection dataInput
Connection method: Screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.25 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 2.5 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.25 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 2.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 14
Stripping length: 6.5 mm
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
Output
Connection method: Screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 2.5 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 2.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.25 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 2.5 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.25 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 2.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 14
Stripping length: 6.5 mm
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
Signal
Connection method: Push-in connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 1 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 1.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.2 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 0.75 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.2 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 1.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 16
Stripping length: 8 mm
SignalingTypes of signaling: LED
Floating signal contact
Active signal output Out1 (digital, configurable)
Active signal output Out2 (analog, configurable)
Remote contact
Signal ground SGnd
Signal output
POut: > 100Â% (LED lights up yellow, output power > 180ÂW)
> 75Â% (LED lights up green, output power > 135ÂW)
> 50Â% (LED lights up green, output power > 90ÂW)
UOut: > 0.9ÂxÂUSet (LED lights up green)
< 0.9ÂxÂUSet (LED flashes green)
Electrical propertiesNumber of phases: 1.00
Insulation voltage input/output: 4 kV AC (type test)
2 kV AC (routine test)
Insulation voltage output / PE: 0.5 kV DC (type test)
0.5 kV DC (routine test)
Insulation voltage input / PE: 3.5 kV AC (type test)
2.4 kV AC (routine test)
Switching frequency: 90 kHz ... 110 kHz (Auxiliary converter stage)
52 kHz ... 260 kHz (Main converter stage)
35 kHz ... 700 kHz (PFC stage)
Product propertiesProduct type: Power supply
Product family: QUINT POWER
MTBF (IEC 61709, SN 29500): > 1196000 h (25°C)
> 749000 h (40°C)
> 355000 h (60°C)
Environmental protection directive: RoHS Directive 2011/65/EU
WEEE
Reach
Insulation characteristics
Protection class: I
Degree of pollution: 2
Life expectancy (electrolytic capacitors)
Current: 7.5 A
Temperature: 40°C
Time: 290000 h
Additional text: 120ÂVÂAC
Life expectancy (electrolytic capacitors)âۉ€¹
Current: 7.5 A
Temperature: 40°C
Time: 288000 h
Additional text: 230ÂVÂAC
Life expectancy (electrolytic capacitors)âۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Current: 15 A
Temperature: 25°C
Time: 303000 h
Additional text: 120ÂVÂAC
Life expectancy (electrolytic capacitors)âۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Current: 15 A
Temperature: 25°C
Time: 331000 h
Additional text: 230ÂVÂAC
Life expectancy (electrolytic capacitors)âۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Current: 15 A
Temperature: 40°C
Time: 107000 h
Additional text: 120ÂVÂAC
Life expectancy (electrolytic capacitors)âۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Current: 15 A
Temperature: 40°C
Time: 117000 h
Additional text: 230ÂVÂAC
DimensionsDimensional drawing: https://dam-mdc.phoenixcontact.com/rendition/156443151564/247c8d3f3703dd4c98fe02eba0e6a6b0/-S204x204-FJPG
Width: 50 mm
Height: 130 mm
Depth: 125 mm
Installation dimensions
Installation distance right/left: 5 mm / 5 mm
Installation distance top/bottom: 50 mm / 50 mm
Alternative assembly
Width: 122 mm
Height: 130 mm
Depth: 53 mm
MountingMounting type: DIN rail: 35 mm
Assembly instructions: alignable: PN ≥50%, 5Âmm horizontally, 15Âmm next to active components, 50Âmm vertically
alignable: PN <50%, 0Âmm horizontally, 40Âmm vertically top, 20 mm vertically bottom
Mounting position: horizontal DIN rail NS 35, EN 60715
With protective coating: No
Material specificationsFlammability rating according to ULÂ94 (housing / terminal blocks): V0
Housing material: Metal
Hood version: Stainless steel X6Cr17
Side element version: Aluminum
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -25°C ... 70°C (>Â60°C Derating: 2,5Â%/K)
Ambient temperature (storage/transport): -40°C ... 85°C
Ambient temperature (start-up type tested): -40°C
Maximum altitude: ≤ 5000 m (> 2000 m, observe derating)
Climatic class: 3K3 (in acc. with EN 60721)
Max. permissible relative humidity (operation): ≤ 95 % (at 25°C, non-condensing)
Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation): 5ÂHz ... 100ÂHz resonance search 2.3g, 90Âmin., resonance frequency 2.3g, 90Âmin. (according to DNV GL Class C)
Standards and regulationsRail applications: ENÂ50121-3-2
ENÂ50121-4
ENÂ50121-5
IEC 62236-3-2
IEC 62236-4
IEC 62236-5
HART FSK Physical Layer Test Specification Compliance: Output voltage UOut compliant
Standard âۉ€œ Limitation of mains harmonic currents: ENÂ61000-3-2
Standard - Electrical safety: IEC 61010-2-201Â(SELV)
Standard âۉ€œ Safety extra-low voltage: IEC 61010-1 (SELV)
IEC 61010-2-201 (PELV)
Standard - Safe isolation: IEC 61558-2-16
IEC 61010-2-201
Standard - safety for equipment for measurement, control, and laboratory use: IEC 61010-1
Standard - Safety of transformers: ENÂ61558-2-16
Battery charging: DINÂ41773-1
Approval - requirement of the semiconductor industry with regard to mains voltage dips: SEMIÂF47-0706, ENÂ61000-4-11
Overvoltage category
EN 61010-1: IIÂ(≤Â5000Âm)
EN 62477-1: IIIÂ(≤Â2000Âm)
ApprovalsCSA: CAN/CSA-C22.2 No.Â60950-1-07
CSA-C22.2 No.Â107.1-01
UL approvals: UL Listed ULÂ508
UL/C-UL Recognized ULÂ60950-1
UL ANSI/ISA-12.12.01 Class I, Division 2, Groups A, B, C, D (Hazardous Location)
EMC dataLow Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emission: ENÂ61000-6-3
ENÂ61000-6-4
EMC requirements for noise immunity: ENÂ61000-6-1
ENÂ61000-6-2
Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
EMC requirements, power plant: IEC 61850-3
ENÂ61000-6-5
Conducted noise emission: ENÂ55016
ENÂ61000-6-3 (Class B)
Noise emission: Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply)
ENÂ55016
ENÂ61000-6-3 (Class B)
Harmonic currents
Standards/regulations: ENÂ61000-3-2
ENÂ61000-3-2 (Class A)
Frequency range: 0 kHz ... 2 kHz
Flicker
Standards/regulations: ENÂ61000-3-3
Frequency range: 0 kHz ... 2 kHz
Electrostatic discharge
Standards/regulations: ENÂ61000-4-2
Electrostatic dischargeâۉ€¹
Contact discharge: 8 kV (Test Level 4)
Discharge in air: 15 kV (Test Level 4)
Comments: Criterion A
Electromagnetic HF field
Standards/regulations: ENÂ61000-4-3
Electromagnetic HF fieldâۉ€¹
Frequency range: 80 MHz ... 1 GHz
1 GHz ... 6 GHz
1 GHz ... 6 GHz
Test field strength: 20 V/m (Test Level 3)
10 V/m (Test Level 3)
10 V/m (Test Level 3)
Comments: Criterion A
Fast transients (burst)
Standards/regulations: ENÂ61000-4-4
Fast transients (burst)âۉ€¹
Input: 4 kV (Test Level 4 - asymmetrical)
Output: 4 kV (Test Level 4 - asymmetrical)
Signal: 4 kV (Test Level 4 - asymmetrical)
Comments: Criterion A
Surge voltage load (surge)
Input: 3 kV (Test Level 4 - symmetrical)
6 kV (Test Level 4 - asymmetrical)
Output: 0.5 V (Test Level 2 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Signal: 4 kV (Test Level 4 - asymmetrical)
Comments: Criterion A
Conducted interference
Standards/regulations: ENÂ61000-4-6
Conducted interferenceâۉ€¹
I/O/S: asymmetrical
Frequency range: 0.15 MHz ... 80 MHz
Comments: Criterion A
Voltage: 10 V (Test Level 3)
Power frequency magnetic field
Standards/regulations: ENÂ61000-4-8
Frequency: 16.7 Hz
50 Hz
60 Hz
50 Hz
60 Hz
0 Hz
Test field strength: 100 A/m
1 kA/m
300 A/m
Additional text: 60 s
3 s
DC, 60Âs
Comments: Criterion A
Frequency range: 50 Hz ... 60 Hz
Voltage dips
Standards/regulations: ENÂ61000-4-11
Voltage: 230 VÂAC
Frequency: 50 Hz
Voltage dip: 70 %
40 %
0 %
Number of periods: 0.5 / 1 / 25 periods
5 / 10 / 50 periods
0,5 / 1 / 5 / 50 / 250 periods
Additional text: Test Level 2
Comments: Criterion A: 0.5 / 1 / 25 periods
Criterion A
Criterion A: 0.5 / 1 period
Criterion B: 5 / 50 / 250 periods
Pulse-shape magnetic field
Standards/regulations: ENÂ61000-4-9
Test field strength: 1000 A/m
Comments: Criterion A
Attenuated sinusoidal oscillations (ring wave)
Standards/regulations: ENÂ61000-4-12
Input: 2 kV (Test Level 4 - symmetrical)
4 kV (Test Level 4 - asymmetrical)
Comments: Criterion A
Asymmetrical conducted disturbance variables
Standards/regulations: ENÂ61000-4-16
Test level 1: 15 Hz 150 Hz (Test Level 4)
Voltage: 30 V 3 V
3 V
3 V 30 V
30 V
30 V (Permanent)
300 V (1 s)
Test level 2: 150 Hz 1.5 kHz (Test Level 4)
Test level 3: 1.5 kHz 15 kHz (Test Level 4)
Test level 4: 15 kHz 150 kHz (Test Level 4)
Test level 5: 16.7 Hz 50 Hz 60 Hz (Test Level 4)
Test level 6: 16.7 Hz 50 Hz 60 Hz (Test Level 4)
Comments: Criterion A
Attenuated oscillating wave
Standards/regulations: ENÂ61000-4-18
Input, output (test levelÂ1): 100 kHz 1 MHz (Test Level 3 - symmetrical)
Voltage: 1 kV
2.5 kV
1 kV
2.5 kV
Input, output (test levelÂ2): 10 MHz
Input, output (test levelÂ3): 100 kHz 1 MHz (Test Level 3 - asymmetrical)
Signals (test levelÂ1): 100 kHz 1 MHz (Test Level 3 - symmetrical)
Signals (test levelÂ2): 100 kHz 1 MHz (Test Level 3 - asymmetrical)
Comments: Criterion A
Attenuated oscillating magnetic field
Standards/regulations: ENÂ61000-4-10
Test field strength: 110 A/m
Test level 1: 100 kHz
Test level 2: 1 MHz
Comments: Criterion A
Criteria
Criterion A: Normal operating behavior within the specified limits.
Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
Criterion C: Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_00040.pdf

Approvals_00041.pdf

Approvals_00054.pdf

Approvals_00055.pdf

Approvals_00056.pdf

Approvals_00057.pdf

Approvals_01297.pdf

Approvals_01324.pdf

Approvals_01330.pdf

Approvals_01335.pdf

Approvals_01382.pdf

Approvals_01508.pdf

Data_sheet_03840.pdf

Manufacturer_declaration_03134.pdf

Manufacturer_declaration_04806.pdf

Manufacturer_declaration_05498.pdf

Manufacturer_declaration_15948.pdf

Package_slip_02118.pdf

Technical_drawing_39981.pdf

Various_00006.pdf