Automazione Industriale

Meccatroinca

Meccatronica

Sicurezza Industriale

Componenti Quadri

Sensori e Sistemi di Visione

Pneumatica

Network e Comunicazione

Cavi Speciali

Accedi ai servizi

Entra nella tua area riservata

Accedi ai servizi

Entra nella tua area riservata

PHOENIX CONTACT 2904618
PHOENIX CONTACT 2904618
PHOENIX CONTACTNon disponibile

QUINT4-PS/1AC/24DC/40/+ - Power supply unit

Primary-switched QUINT POWER supply for DIN rail mounting, with selectable output characteristic curve and SFB (Selective Fuse Breaking) Technology, protective coating and integrated decoupling MOSFET, input: 1-phase, output: 24 V DC / 40 A
Cod. Articolo: 2904618 copia - copy
Cod. Fornitore: 2904618 copia - copy
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Descrizione
Caratteristiche Tecniche
Input dataControl input (configurable) Rem: Output power ON/OFF (SLEEP MODE)
Default: Output power ON (>40 kΩ/24 V DC/open bridge between Rem and SGnd)
AC operation
Network type: Star network
Nominal input voltage range: 100 V AC ... 240 V AC
Input voltage range: 100 V AC ... 240 V AC -15 % ... +10 %
Derating: < 100 V AC (1 %/V)
Electric strength, max.: 300 V AC 60 s
Typical national grid voltage: 120 V AC
230 V AC
Voltage type of supply voltage: AC
Inrush current: typ. 12 A (at 25 °C)
Inrush current integral (I2t): < 0.3 A2s
Inrush current limitation: 12 A (after 1 ms)
AC frequency range: 50 Hz ... 60 Hz -10 % ... +10 %
Frequency range (fN): 50 Hz ... 60 Hz -10 % ... +10 %
16.7 Hz (acc. to EN 50163)
Mains buffering time: typ. 27 ms (120 V AC)
typ. 27 ms (230 V AC)
Current consumption: 13.6 A (100 V AC)
9.9 A (120 V AC)
5.4 A (230 V AC)
5.4 A (240 V AC)
Nominal power consumption: 1072 VA
Protective circuit: Transient surge protection; Varistor, gas-filled surge arrester
Switch-on time: < 1 s
Typical response time: 300 ms (from SLEEP MODE)
Input fuse: 16 A (slow-blow, internal)
Recommended breaker for input protection: 16 A ... 20 A (Characteristic B, C, D, K or comparable)
Discharge current to PE: < 3.5 mA
1.7 mA (264 V AC, 60 Hz)
DC operation
Nominal input voltage range: 110 V DC ... 250 V DC
Input voltage range: 110 V DC ... 250 V DC -18 % ... +40 %
Derating: < 110 V DC (1 %/V)
Voltage type of supply voltage: DC
Current consumption: 12 A (110 V DC)
5 A (250 V DC)
Output dataEfficiency: typ. 94.7 % (120 V AC)
typ. 95.7 % (230 V AC)
Output characteristic: U/I Advanced
Smart HICCUP
FUSE MODE
Nominal output voltage: 24 V DC
Setting range of the output voltage (USet): 24 V DC ... 28 V DC (constant capacity)
Nominal output current (IN): 40 A
Static Boost (IStat.Boost): 45 A
Dynamic Boost (IDyn.Boost): 60 A (5 s)
Selective Fuse Breaking (ISFB): 215 A (15 ms)
Magnetic circuit breaker tripping: A1...A40 / B2...B25 / C1...C13 / Z1...Z16
Derating: > 60 °C ... 70 °C (2.5 %/K)
Feedback voltage resistance: ≤ 35 V DC
Protection against overvoltage at the output (OVP): < 30 V DC (double protection with shut off within 20 ms)
Control deviation: < 0.5 % (Static load change 10 % ... 90 %)
< 2 % (Dynamic load change 10 % ... 90 %, (10 Hz))
< 0.25 % (change in input voltage ±10 %)
Residual ripple: < 40 mVPP (with nominal values)
Short-circuit-proof: yes
No-load proof: yes
Output power: 960 W
1080 W
1440 W
Maximum no-load power dissipation: < 5 W (120 V AC)
< 5 W (230 V AC)
Power loss nominal load max.: < 55 W (120 V AC)
< 44 W (230 V AC)
Power dissipation SLEEP MODE: < 3 W (120 V AC)
< 3 W (230 V AC)
Crest factor: typ. 1,7 (120 V AC)
typ. 1.65 (230 V AC)
Rise time: < 60 ms (UOut = 10 % ... 90 %)
Connection in parallel: yes, for redundancy and increased capacity
Connection in series: yes
Signal
Signal ground SGnd: Reference potential for Out1, Out2, and Rem
Signal Out 1 (configurable)
Digital: 24 V DC 20 mA
Default: 24 V DC 20 mA 24 V DC for UOut > 0.9 x USet
Signal Out 2 (configurable)
Digital: 24 V DC 20 mA
Analog: 4 mA ... 20 mA ±5 % (Load ≤400 Ω)
Default: 24 V DC 20 mA 24 V DC for POut < PN
Signal relay 13/14 (configurable)
Default: closed (Uout > 0.9 USet)
Digital: 24 V DC 1 A
30 V AC/DC 0.5 A
Connection dataInput
Connection method: Screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 6 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 4 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.25 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 4 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.25 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 4 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 10
Stripping length: 8 mm
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
Output
Connection method: Screw connection
Conductor cross section, rigid min.: 0.5 mm²
Conductor cross section, rigid max.: 16 mm²
Conductor cross section flexible min.: 0.5 mm²
Conductor cross section flexible max.: 16 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 16 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.5 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 16 mm²
Conductor cross section AWG min.: 20
Conductor cross section AWG max.: 6
Stripping length: 10 mm
Tightening torque, min: 1.2 Nm
Tightening torque max: 1.5 Nm
Signal
Connection method: Push-in connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 1 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 1.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.2 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 0.75 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.2 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 1.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 16
Stripping length: 8 mm
SignalingTypes of signaling: LED
Floating signal contact
Active signal output Out1 (digital, configurable)
Active signal output Out2 (analog, configurable)
Remote contact
Signal ground SGnd
Signal output
POut: > 100 % (LED lights up yellow, output power > 960 W)
> 75 % (LED lights up green, output power > 720 W)
> 50 % (LED lights up green, output power > 480 W)
UOut: > 0.9 x USet (LED lights up green)
< 0.9 x USet (LED flashes green)
Electrical propertiesNumber of phases: 1.00
Insulation voltage input/output: 4 kV AC (type test)
2 kV AC (routine test)
Switching frequency: 85.00 kHz ... 107.00 kHz (Auxiliary converter stage)
45.00 kHz ... 200.00 kHz (Main converter stage)
50.00 kHz ... 500.00 kHz (PFC stage)
Product propertiesProduct type: Power supply
Product family: QUINT POWER
MTBF (IEC 61709, SN 29500): > 908000 h (25 °C)
> 539000 h (40 °C)
> 243000 h (60 °C)
Data management status
Article revision: 00
Insulation characteristics
Protection class: I
Degree of pollution: 2
Life expectancy (electrolytic capacitors)
Current: 20 A
Temperature: 40 °C
Time: 360000 h
Additional text: 120 V AC
Life expectancy (electrolytic capacitors)âۉ€¹
Current: 20 A
Temperature: 40 °C
Time: 455000 h
Additional text: 230 V AC
Life expectancy (electrolytic capacitors)âۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Current: 40 A
Temperature: 25 °C
Time: 389000 h
Additional text: 120 V AC
Life expectancy (electrolytic capacitors)âۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Current: 40 A
Temperature: 25 °C
Time: 460000 h
Additional text: 230 V AC
Life expectancy (electrolytic capacitors)âۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Current: 40 A
Temperature: 40 °C
Time: 137000 h
Additional text: 120 V AC
Life expectancy (electrolytic capacitors)âۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Current: 40 A
Temperature: 40 °C
Time: 162000 h
Additional text: 230 V AC
DimensionsWidth: 120 mm
Height: 130 mm
Depth: 140 mm
Installation dimensions
Installation distance right/left: 5 mm / 5 mm
Installation distance top/bottom: 50 mm / 50 mm
MountingMounting type: DIN rail mounting
Assembly note: alignable: PN ≥50%, 5 mm horizontally, 15 mm next to active components, 50 mm vertically
alignable: PN <50%, 0 mm horizontally, 40 mm vertically top, 20 mm vertically bottom
Mounting position: horizontal DIN rail NS 35, EN 60715
With protective coating: yes
Material specificationsFlammability rating according to UL 94 (housing / terminal blocks): V0
Housing material: Metal
Hood version: Stainless steel X6Cr17
Side element version: Aluminum
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -40 °C ... 75 °C (> 60 °C Derating: 2,5 %/K)
Ambient temperature (storage/transport): -40 °C ... 85 °C
Maximum altitude: ≤ 5000 m (> 2000 m, observe derating)
Climatic class: 3K22 (in accordance with EN 60721-3-3)
Max. permissible relative humidity (operation): ≤ 100 % (at 25 °C, non-condensing)
Shock: 11 ms, 15 g, in each space direction (according to IEC 60068-2-27)
Vibration (operation): 5 Hz ... 100 Hz resonance search 0.7g, 90 min., resonance frequency 0.7g, 90 min. (in accordance with DNV GL Class A)
5 Hz ... 100 Hz resonance search 2.3g, 90 min., resonance frequency 2.3g, 90 min. (according to DNV GL Class C) mounted with UWA 130 - 2901664
Standards and regulationsRail applications: EN 50121-3-2
EN 50121-4
EN 50121-5
EN 50163
IEC 62236-3-2
IEC 62236-4
IEC 62236-5
EN 50155
EN 45545-2 (HL3)
EN 61373 (Class 1B)
HART FSK Physical Layer Test Specification Compliance: Output voltage UOut compliant
Standard âۉ€œ Limitation of mains harmonic currents: EN 61000-3-2
Standard - Electrical safety: IEC 61010-2-201 (SELV)
Explosive atmosphere: IEC 60079-0
IEC 60079-7
IEC 60079-11
IEC 60079-15
Standard âۉ€œ Safety extra-low voltage: IEC 61010-1 (SELV)
IEC 61010-2-201 (PELV)
Standard - Safe isolation: IEC 61558-2-16
IEC 61010-2-201
Standard - safety for equipment for measurement, control, and laboratory use: IEC 61010-1
Battery charging: DIN 41773-1
Approval - requirement of the semiconductor industry with regard to mains voltage dips: SEMI F47-0706, EN 61000-4-11
Overvoltage category
EN 61010-1: II (≤ 5000 m)
EN 62477-1: III (≤ 2000 m)
EN 61558-2-16: II (≤ 5000 m)
Fire protection in rail vehicles
Standard designation: Fire protection in rail vehicles
Standards/specifications: EN 45545-2 (HL3)
ApprovalsCSA: CAN/CSA-C22.2 No. 61010-2-201
CSA-C22.2 No. 107.1-16
Shipbuilding approval: DNV
SIQ: CB-Scheme (IEC 61010-1, IEC 61010-2-201)
UL approvals: UL Listed UL 508
UL 121201 & CSA C22.2 No. 213-17 Class I, Division 2, Groups A, B, C, D T4 (Hazardous Location) applied for
Conformity/Approvals
ATEX: SIQ 23 ATEX 161 X
ïÃ‹œ II 3 G Ex ec ic nC IIC T4 Gc
INMETRO: DNV 19.0187 X
IECEx: IECEx SIQ 23.0001X
Ex ec ic nC IIC T4 Gc
Functional Safety in accordance with IEC 61508: SIL 3 applied for
EMC dataElectromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
Low Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emission: EN 61000-6-3
EN 61000-6-4
EMC requirements for noise immunity: EN 61000-6-1
EN 61000-6-2
EMC requirements for power supply: IEC 61850-3 (G,H)
EN 61000-6-5 (switching devices)
Conducted noise emission: EN 55016
EN 61000-6-3 (Class B)
Noise emission: Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply)
EN 55016
EN 61000-6-3 (Class B)
DNV GL conducted interference: Class A
Additional text: Area power distribution
DNV GL noise radiation: Class A
Harmonic currents
Standards/regulations: EN 61000-3-2
EN 61000-3-2 (Class A)
Frequency range: 0 kHz ... 2 kHz
Flicker
Standards/regulations: EN 61000-3-3
Frequency range: 0 kHz ... 2 kHz
Electrostatic discharge
Standards/regulations: EN 61000-4-2
Electrostatic dischargeâۉ€¹
Contact discharge: 8 kV (Test Level 4)
Discharge in air: 15 kV (Test Level 4)
Comments: Criterion A
Electromagnetic HF field
Standards/regulations: EN 61000-4-3
Electromagnetic HF fieldâۉ€¹
Frequency range: 80 MHz ... 1 GHz
1 GHz ... 6 GHz
Test field strength: 20 V/m (Test Level 3)
10 V/m (Test Level 3)
Comments: Criterion A
Fast transients (burst)
Standards/regulations: EN 61000-4-4
Fast transients (burst)âۉ€¹
Input: 4 kV (Test Level 4 - asymmetrical)
Output: 4 kV (Test Level 4 - asymmetrical)
Signal: 4 kV (Test Level 4 - asymmetrical)
Comments: Criterion A
Surge voltage load (surge)
Standards/regulations: EN 61000-4-5
Surge voltage load (surge)âۉ€¹
Input: typ. 3 kV (Test Level 4 - symmetrical)
typ. 6 kV (Test Level 4 - asymmetrical)
Output: 1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Signal: 4 kV (Test Level 4 - asymmetrical)
Comments: Criterion A
Conducted interference
Standards/regulations: EN 61000-4-6
Conducted interferenceâۉ€¹
I/O/S: asymmetrical
Frequency range: 0.15 MHz ... 80 MHz
Comments: Criterion A
Voltage: 10 V (Test Level 3)
Power frequency magnetic field
Standards/regulations: EN 61000-4-8
Frequency: 16.7 Hz
50 Hz
60 Hz
50 Hz
60 Hz
0 Hz
Test field strength: 100 A/m
1 kA/m
300 A/m
Additional text: 60 s
3 s
DC, 60 s
Comments: Criterion A
Frequency range: 50 Hz ... 60 Hz
Voltage dips
Standards/regulations: EN 61000-4-11
Voltage: 230 V AC
Frequency: 50 Hz
Voltage dip: 70 %
40 %
0 %
Number of periods: 0.5 / 1 / 25 / 30 periods
5 / 10 / 50 periods
0,5 / 1 / 5 / 50 / 250 periods
Additional text: Test Level 2
Comments: Criterion A: 0.5 / 1 / 25 / 30 periods
Criterion A
Criterion A: 0.5 / 1 period
Criterion B: 5 / 50 / 250 periods
Pulse-shape magnetic field
Standards/regulations: EN 61000-4-9
Test field strength: 1000 A/m
Comments: Criterion A
Attenuated sinusoidal oscillations (ring wave)
Standards/regulations: EN 61000-4-12
Input: 2 kV (Test Level 4 - symmetrical)
4 kV (Test Level 4 - asymmetrical)
Comments: Criterion A
Asymmetrical conducted disturbance variables
Standards/regulations: EN 61000-4-16
Test level 1: 15 Hz 150 Hz (Test Level 4)
Voltage: 30 V 3 V
3 V
3 V 30 V
30 V
30 V (10 s)
30 V (10 s)
300 V (3 s)
Test level 2: 150 Hz 1.5 kHz (Test Level 4)
Test level 3: 1.5 kHz 15 kHz (Test Level 4)
Test level 4: 15 kHz 150 kHz (Test Level 4)
Test level 5: 16.7 Hz 50 Hz 60 Hz (Test Level 4)
Test level 6: 150 Hz 180 Hz (Test Level 4)
Test level 7: 16.7 Hz 50 Hz 60 Hz (Test Level 4)
Comments: Criterion A
Attenuated oscillating wave
Standards/regulations: EN 61000-4-18
Input, output (test level 1): 100 kHz 1 MHz (Test Level 3 - symmetrical)
Voltage: 1 kV
2 kV
2.5 kV
1 kV
2.5 kV
Input, output (test level 2): 10 MHz (Test Level 3 - asymmetrical)
Input, output (test level 3): 100 kHz 1 MHz (Test Level 3 - asymmetrical)
Signals (test level 1): 100 kHz 1 MHz (Test Level 3 - symmetrical)
Signals (test level 2): 100 kHz 1 MHz (Test Level 3 - asymmetrical)
Comments: Criterion A
Attenuated oscillating magnetic field
Standards/regulations: EN 61000-4-10
Test field strength: 100 A/m
Test level 1: 100 kHz
Test level 2: 1 MHz
Comments: Criterion A
Criteria
Criterion A: Normal operating behavior within the specified limits.
Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
Criterion C: Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
Descrizione
QUINT4-PS/1AC/24DC/40/+ Alimentatore