DEK-OV- 5DC/240AC/800 - Solid-state relay terminal block

Power solid-state relay terminal block, input: 5 V DC, output: 10 - 253 V AC/800 mA, terminal block width: 6.2 mm
Cod. Articolo: 2964623 copia - copy
Cod. Fornitore: 2964623 copia - copy
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Download
Caratteristiche Tecniche
NotesGeneral: The housing is open on one side. The appropriate cover is D-DEK 1,5 GN (2716949).
Use of EB 80-DIK... bridges in the DEK terminal blocks: Absorption of humidity from the ambient air as well as an unfavorable tolerance between a larger number of DEK terminal blocks and the EB 80-DIK... bridge may cause (minor) expansion of the DEK housing. When the EB 80-DIK... bridges are used, therefore, it is recommended that these be disconnected after about 10 to 12 DEK terminal blocks and a wire bridge to the next DEK terminal block be inserted in their place.
Product propertiesProduct type: Solid-state relay module
Product family: DEK
Application: Output function
Operating mode: 100% operating factor
Insulation characteristics
Insulation: Basic insulation
Insulation characteristics: Standards/regulations
Insulation: Basic insulation
Overvoltage category: III
Pollution degree: 2
Electrical propertiesTest voltage (Input/output): 2.5 kV AC (50ÂHz, 1Âmin., input/output)
Input dataNominal input voltage UN: 5 VÂDC
Input voltage range in reference to UN: 0.8 ... 1.2
Input voltage range: 4 VÂDC ... 6 VÂDC
Switching threshold "0" signal in reference to UN: ≤ 0.4
Switching threshold "1" signal in reference to UN: ≥ 0.8
Typical input current at UN: 10.2 mA
Typical response time: < 10 ms
Typical turn-off time: < 10 ms
Operating voltage display: Yellow LED
Protective circuit: Reverse polarity protection; Polarity protection diode
Surge protection
Transmission frequency: 10 Hz
Output dataContact switching type: 1 N/O contact
Design of digital output: electronic
Output voltage range: 10 VÂAC ... 253 VÂAC (50/60ÂHz)
Limiting continuous current: 0.8 A (see derating curve)
Maximum inrush current: 30 A (tÂ=Â10Âms)
Min. load current: 10 mA
Leakage current: 1.2 mA
Surge current: 30 A (tÂ=Â10Âms)
Phase angle cos phi min: 0.5
Max. load value: 4.5 A2s
Peak offstate voltage: 600 V (Periodic peak reverse voltage)
Voltage drop at max. limiting continuous current: ≤ 1 V
Output circuit: 2-conductor floating, zero voltage switch
Protective circuit: RCV circuit; RCV circuit
Connection dataConnection method: Screw connection
Stripping length: 8 mm
Screw thread: M3
Conductor cross section rigid: 0.2 mm² ... 2.5 mm²
Conductor cross section flexible: 0.2 mm² ... 2.5 mm²
Conductor cross section AWG: 24 ... 14
Tightening torque: 0.5 Nm
DimensionsWidth: 6.2 mm
Height: 80 mm
Depth: 56 mm
Environmental and real-life conditionsAmbient conditions
Ambient temperature (operation): -20°C ... 60°C
Ambient temperature (storage/transport): -20°C ... 70°C
Standards and regulationsStandards/regulations
Standards/regulations: IEC 60947-5-1
MountingMounting type: DIN rail mounting
Assembly instructions: in rows with zero spacing
Mounting position: any