PHOENIX CONTACT 1151048
PHOENIX CONTACT 1151048
PHOENIX CONTACTNon disponibile

QUINT4-PS/3AC/24DC/20/IOL - Power supply unit

Primary-switched power supply unit QUINT POWER, Screw connection, DIN rail mounting, input:3-phase, output: 24 VDC / 20 A
Cod. Articolo: 1151048 copia - copy
Cod. Fornitore: 1151048 copia - copy
PHOENIX CONTACT


Diminuisci la quantità
Aumenta la quantità
Caratteristiche Tecniche
Download
Caratteristiche Tecniche
Input dataAC operation
Network type: Star network
Nominal input voltage range: 3x 400 VÂAC ... 500 VÂAC
2x 400 VÂAC ... 500 VÂAC
Input voltage range: 3x 400 VÂAC ... 500 VÂAC -20Â%Â...Â+10Â%
2x 400 VÂAC ... 500 VÂAC -10Â%Â...Â+10Â%
Typical national grid voltage: 400 VÂAC
480 VÂAC
Voltage type of supply voltage: AC/DC
Inrush current: typ. 2 A (at 25°C)
Inrush current integral (I2t): < 0.1 A2s
Inrush current limitation: 2 A (after 1Âms)
AC frequency range: 50 Hz ... 60 Hz -10Â%Â...Â+10Â%
Frequency range (fN): 50 Hz ... 60 Hz -10Â%Â...Â+10Â%
Mains buffering time: typ. 33 ms (3x 400 V AC)
typ. 33 ms (3x 480 V AC)
Current consumption: 3x 0.99 A (400ÂVÂAC)
3x 0.81 A (480ÂVÂAC)
2x 1.62 A (400ÂVÂAC)
2x 1.37 A (480ÂVÂAC)
3x 0.8 A (500 V AC)
2x 1.23 A (500 V AC)
Reverse polarity protection: yes
Nominal power consumption: 541 VA
Protective circuit: Transient surge protection; Varistor, gas-filled surge arrester
Power factor (cos phi): 0.94
Switch-on time: < 1 s
Typical response time: 300 ms (from SLEEP MODE)
Recommended breaker for input protection: 3x 4 A ... 20 A (Characteristic B, C or comparable)
Recommended fuse for input protection: ≥ 300 VÂAC
Discharge current to PE: < 3.5 mA
1.7 mA (550 V AC, 60 Hz)
DC operation
Nominal input voltage range: ± 260 VÂDC ... 300 VÂDC
Input voltage range: ± 260 VÂDC ... 300 VÂDC -13Â%Â...Â+30Â%
Current consumption: 1.23 A (±Ã‚260ÂVÂDC)
1.06 A (±300ÂVÂDC)
Recommended breaker for input protection: 1x 6 A (10 x 38 mm, 30 kA L/R = 2 ms)
Recommended fuse for input protection: ≥ 1000 VÂDC
Output dataEfficiency: typ. 94.1 % (400ÂVÂAC)
typ. 94.9 % (480ÂVÂAC)
Output characteristic: U/I Advanced
Nominal output voltage: 24 VÂDC
Setting range of the output voltage (USet): 24 VÂDC ... 29.5 VÂDC (constant capacity)
Nominal output current (IN): 20 A
Static Boost (IStat.Boost): 25 A
Dynamic Boost (IDyn.Boost): 30 A (5 s)
Selective Fuse Breaking (ISFB): 120 A (15 ms)
Magnetic circuit breaker tripping: A1...A16 / B2...B13 / C1...C6 / Z1...Z16
Derating: > 60°C ... 70°C (2.5%/K)
Feedback voltage resistance: ≤ 35 VÂDC
Protection against overvoltage at the output (OVP): ≤ 32 VÂDC
Control deviation: < 0.5 % (Static load change 10Â% ... 90Â%)
< 3 % (Dynamic load change 10Â% ... 90Â%, (10 Hz))
< 0.25 % (change in input voltage ±10 %)
Residual ripple: < 60 mVPP (with nominal values)
Short-circuit-proof: yes
No-load proof: yes
Output power: 480 W
600 W
720 W
Apparent power: 686 VA (400ÂV, UOUT = 24ÂV, IOUT = stat. Boost)
698 VA (480ÂV, UOUT = 24ÂV, IOUT = stat. Boost)
Maximum no-load power dissipation: < 6 W (400ÂVÂAC)
< 6 W (480ÂVÂAC)
Power loss nominal load max.: < 30 W (400ÂVÂAC)
< 30 W (480ÂVÂAC)
Power dissipation SLEEP MODE: < 5 W (400ÂVÂAC)
< 5 W (480ÂVÂAC)
Crest factor: typ. 1.78 (400ÂVÂAC)
typ. 2.1 (480ÂVÂAC)
Rise time: < 80 ms (UOutÂ=Â10Â%Â...Â90Â%)
Connection in parallel: yes, for redundancy and increased capacity
Connection in series: yes
Signal relay 13/14 (configurable)
Default: closed (Uout > 0.9 USet)
Digital: 24 VÂDC 1 A
30 V AC/DC 0.5 A
Connection dataInput
Connection method: Screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 6 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 4 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.25 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 4 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.25 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 4 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 10
Stripping length: 8 mm
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
Output
Connection method: Screw connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 6 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 4 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.25 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 4 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.25 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 4 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 10
Stripping length: 8 mm
Tightening torque, min: 0.5 Nm
Tightening torque max: 0.6 Nm
Signal
Connection method: Push-in connection
Conductor cross section, rigid min.: 0.2 mm²
Conductor cross section, rigid max.: 1 mm²
Conductor cross section flexible min.: 0.2 mm²
Conductor cross section flexible max.: 1.5 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, min.: 0.2 mm²
Single conductor/flexible terminal point with ferrule with plastic sleeve, max.: 0.75 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, min.: 0.2 mm²
Single conductor/flexible terminal point with ferrule without plastic sleeve, max.: 1.5 mm²
Conductor cross section AWG min.: 24
Conductor cross section AWG max.: 16
Stripping length: 8 mm
InterfacesIO-Link
Reverse polarity protection: yes
IO-Linkâۉ€¹
Specification: V1.1
Interface: IO-Link
Connection method: 3-conductor port classÂA
Connection marking: 3.3 (L+)
3.4 (ï¡Ã¢„¢)
3.5 (L-)
Transmission speed: 230 kbps (COM3)
Cycle time: 2 ms
Electrical isolation: yes
Amount of process data: 6 Byte (Input data)
Device ID: 262657dec/ 0x040201hex
Vendor ID: 00B0hex / 176dez
System communication
Interface: System communication
Connection method: 2-conductor
Connection marking: 3.6 (ï¡Ã‹œ)
3.5 (L-/Sgnd)
Electrical isolation: yes
SignalingSignal output
POut: > 100Â% (LED lights up yellow, output power > 480ÂW)
> 75Â% (LED lights up green, output power > 360ÂW)
> 50Â% (LED lights up green, output power > 240ÂW)
UOut: > 0.9ÂxÂUSet (LED lights up green)
< 0.9ÂxÂUSet (LED flashes green)
Electrical propertiesNumber of phases: 3.00
Insulation voltage input/output: 4 kV AC (type test)
2.4 kV AC (routine test)
Insulation voltage output / PE: 0.5 kV DC (type test)
0.5 kV DC (routine test)
Insulation voltage input / PE: 3.5 kV AC (type test)
2.4 kV AC (routine test)
Switching frequency: 90 kHz ... 110 kHz (Auxiliary converter stage)
56 kHz ... 500 kHz (Main converter stage)
25 kHz ... 500 kHz (PFC stage)
Product propertiesProduct type: Power supply
Product family: QUINT POWER
MTBF (IEC 61709, SN 29500): > 985000 h (25°C)
> 638000 h (40°C)
> 311000 h (60°C)
Environmental protection directive: RoHS Directive 2011/65/EU
WEEE
Reach
Insulation characteristics
Protection class: I
Degree of pollution: 2
Life expectancy (electrolytic capacitors)
Current: 10 A
Temperature: 40°C
Time: 344000 h
Additional text: 400ÂVÂAC
Life expectancy (electrolytic capacitors)âۉ€¹
Current: 10 A
Temperature: 40°C
Time: 320000 h
Additional text: 480ÂVÂAC
Life expectancy (electrolytic capacitors)âۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Current: 20 A
Temperature: 25°C
Time: 445000 h
Additional text: 400ÂVÂAC
Life expectancy (electrolytic capacitors)âۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Current: 20 A
Temperature: 25°C
Time: 432000 h
Additional text: 480ÂVÂAC
Life expectancy (electrolytic capacitors)âۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Current: 20 A
Temperature: 40°C
Time: 157000 h
Additional text: 400ÂVÂAC
Life expectancy (electrolytic capacitors)âۉ€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹Ãƒ¢Ã¢‚¬Ã¢€¹
Current: 20 A
Temperature: 40°C
Time: 152000 h
Additional text: 480ÂVÂAC
DimensionsWidth: 70 mm
Height: 130 mm
Depth: 125 mm
Installation dimensions
Installation distance right/left: 5 mm / 5 mm
Installation distance top/bottom: 50 mm / 50 mm
MountingMounting type: DIN rail mounting
Mounting position: horizontal DIN rail NS 35, EN 60715
With protective coating: No
Material specificationsFlammability rating according to ULÂ94 (housing / terminal blocks): V0
Housing material: Metal
Hood version: Stainless steel X6Cr17
Side element version: Aluminum
Environmental and real-life conditionsAmbient conditions
Degree of protection: IP20
Ambient temperature (operation): -25°C ... 70°C (>Â60°C Derating: 2,5Â%/K)
Ambient temperature (storage/transport): -40°C ... 85°C
Ambient temperature (start-up type tested): -40°C
Maximum altitude: ≤ 5000 m (> 2000 m, observe derating)
Climatic class: 3K22 (in accordance with ENÂ60721-3-3)
Max. permissible relative humidity (operation): ≤ 95 % (at 25°C, non-condensing)
Shock: 18 ms, 30g, in each space direction (according to IEC 60068-2-27)
Vibration (operation): 5ÂHz ... 100ÂHz resonance search 2.3g, 90Âmin., resonance frequency 2.3g, 90Âmin. (according to DNV GL Class C)
Standards and regulationsRail applications: ENÂ50121-3-2
ENÂ50121-5
IEC 62236-3-2
IEC 62236-5
HART FSK Physical Layer Test Specification Compliance: Output voltage UOut compliant
Standard âۉ€œ Limitation of mains harmonic currents: ENÂ61000-3-2
Standard - Electrical safety: IEC 60950-1/VDEÂ0805 (SELV)
Standard âۉ€œ Safety extra-low voltage: IEC 61010-1 (SELV)
IEC 61010-2-201 (PELV)
Standard - Safe isolation: IEC 61558-2-16
IEC 61010-2-201
Standard - safety for equipment for measurement, control, and laboratory use: IEC 61010-1
Standard - Safety of transformers: ENÂ61558-2-16
Standard - power supply devices for low voltage with DC output: ENÂ61204-3
Battery charging: DINÂ41773-1
Approval - requirement of the semiconductor industry with regard to mains voltage dips: SEMIÂF47-0706, ENÂ61000-4-11
Overvoltage category
EN 61010-1: IIÂ(≤Â5000Âm)
EN 62477-1: IIIÂ(≤Â2000Âm)
ENÂ61558-2-16: IIÂ(≤Â5000Âm)
ApprovalsCSA: CAN/CSA-C22.2 No.Â61010-1-12
CAN/CSA-C22.2 No.Â61010-2-201
SIQ: CB-Scheme (IEC 61010-1, IEC 61010-2-201)
UL approvals: UL Listed ULÂ61010-1
UL Listed ULÂ61010-2-201
ULÂ121201 & CSAÂC22.2ÂNo.Â213-17 ClassÂI, DivisionÂ2, Groups A, B, C, D T4 (Hazardous Location)
EMC dataLow Voltage Directive: Conformance with Low Voltage Directive 2014/35/EC
EMC requirements for noise emission: ENÂ61000-6-3
ENÂ61000-6-4
EMC requirements for noise immunity: ENÂ61000-6-1
ENÂ61000-6-2
Electromagnetic compatibility: Conformance with EMC Directive 2014/30/EU
EMC requirements, power plant: ENÂ61000-6-5
Conducted noise emission: ENÂ55016
ENÂ61000-6-3 (Class B)
Noise emission: Additional basic standard EN 61000-6-5 (immunity in power station), IEC/EN 61850-3 (energy supply)
ENÂ55016
ENÂ61000-6-3 (Class B)
Harmonic currents
Standards/regulations: ENÂ61000-3-2
ENÂ61000-3-2 (Class A)
Frequency range: 0 kHz ... 2 kHz
Flicker
Standards/regulations: ENÂ61000-3-3
Frequency range: 0 kHz ... 2 kHz
Electrostatic discharge
Standards/regulations: ENÂ61000-4-2
Electrostatic dischargeâۉ€¹
Contact discharge: 8 kV (Test Level 4)
Discharge in air: 15 kV (Test Level 4)
Comments: Criterion A
Electromagnetic HF field
Standards/regulations: ENÂ61000-4-3
Electromagnetic HF fieldâۉ€¹
Frequency range: 80 MHz ... 1 GHz
1 GHz ... 6 GHz
Test field strength: 20 V/m (Test Level 3)
10 V/m (Test Level 3)
Comments: Criterion A
Fast transients (burst)
Standards/regulations: ENÂ61000-4-4
Fast transients (burst)âۉ€¹
Input: 4 kV (Test Level 4 - asymmetrical)
Output: 2 kV (Test Level 4 - asymmetrical)
Signal: 2 kV (Test Level 4 - asymmetrical)
Comments: Criterion B
Surge voltage load (surge)
Standards/regulations: ENÂ61000-4-5
Input: 2 kV (Test Level 3 - symmetrical)
6 kV (Test Level 4 - asymmetrical)
Output: 1 kV (Test Level 3 - symmetrical)
2 kV (Test Level 3 - asymmetrical)
Signal: 1 kV (Test Level 2 - asymmetrical)
Comments: Criterion B
Conducted interference
Standards/regulations: ENÂ61000-4-6
Conducted interferenceâۉ€¹
I/O/S: asymmetrical
Frequency range: 0.15 MHz ... 80 MHz
Comments: Criterion A
Voltage: 10 V (Test Level 3)
Power frequency magnetic field
Standards/regulations: ENÂ61000-4-8
Frequency: 16.7 Hz
50 Hz
60 Hz
50 Hz
60 Hz
0 Hz
Test field strength: 100 A/m
1 kA/m
300 A/m
Additional text: 60 s
3 s
DC, 60Âs
Comments: Criterion A
Frequency range: 50 Hz ... 60 Hz
Voltage dips
Standards/regulations: ENÂ61000-4-11
Voltage: 400 VÂAC
Frequency: 50 Hz
Voltage dip: 70 %
40 %
0 %
Number of periods: 0.5 / 1 / 25 periods
5 / 10 / 50 periods
0,5 / 1 / 5 / 50 / 250 periods
Additional text: Test Level 2
Comments: Criterion A: 0.5 / 1 period
Criterion B: 25 periods
Criterion B
Criterion A: 0.5 / 1 period
Criterion B: 5 / 50 / 250 periods
Pulse-shape magnetic field
Standards/regulations: ENÂ61000-4-9
Test field strength: 1000 A/m
Comments: Criterion A
Attenuated sinusoidal oscillations (ring wave)
Standards/regulations: ENÂ61000-4-12
Input: 2 kV (Test Level 4 - symmetrical)
4 kV (Test Level 4 - asymmetrical)
Comments: Criterion A
Asymmetrical conducted disturbance variables
Standards/regulations: ENÂ61000-4-16
Test level 1: 15 Hz 150 Hz (Test Level 3)
Voltage: 10 V 1 V
1 V
1 V 10 V
10 V
10 V (Permanent)
100 V (1 s)
Test level 2: 150 Hz 1.5 kHz (Test Level 3)
Test level 3: 1.5 kHz 15 kHz (Test Level 3)
Test level 4: 15 kHz 150 kHz (Test Level 3)
Test level 5: 50 Hz 60 Hz (Test Level 3)
Test level 6: 50 Hz 60 Hz (Test Level 3)
Comments: Criterion A
Attenuated oscillating magnetic field
Standards/regulations: ENÂ61000-4-10
Test field strength: 100 A/m
Test level 1: 100 kHz
Test level 2: 1 MHz
Comments: Criterion A
Criteria
Criterion A: Normal operating behavior within the specified limits.
Criterion B: Temporary impairment to operational behavior that is corrected by the device itself.
Criterion C: Temporary adverse effects on the operating behavior, which the device corrects automatically or which can be restored by actuating the operating elements.
Download
PER SCARICARE I DOCUMENTI E' NECESSARIO EFFETTUARE L'ACCESSO AL SITO

Approvals_01297.pdf

Approvals_01330.pdf

Approvals_01335.pdf

Approvals_01573.pdf

Data_sheet_00855.pdf

Manufacturer_declaration_03464.pdf

Manufacturer_declaration_03465.pdf

Package_slip_02148.pdf

Technical_drawing_09428.pdf

Various_00006.pdf